![Arcteq AQ F3 0 Series Скачать руководство пользователя страница 124](http://html1.mh-extra.com/html/arcteq/aq-f3-0-series/aq-f3-0-series_instruction-manual_2964933124.webp)
Instruction manual
–
AQ F3x0 Feeder protection IED
124 (162
)
Figure 3-7: Example sag and swell events.
Table 3-66: Sag and swell function setting parameters
Parameter
Setting value, range
and step
Description
Operation
Off
On
Disabling or enabling the operation of the function, Default
setting is Off
Swell limit
50...150% ms by step
of 1 %
Voltage swell limit, above which swell is detected, Default
setting is 110%
Sag limit
30…100% by step of
1%
Voltage sag limit, below which sag is detected, default setting
is 90%
Interruption
limit
10…50% by step of
1%
Voltage interruption limit, below which interruption is detected,
Default setting is 20%
Minimum
duration
30…60000ms by
steps of 1ms
Lower time limit, default setting is 50ms
Maximum
duration
100…60000ms by
step of 1ms
Upper time limit, default setting is 10000ms
3.3.10
D
ISTURBANCE RECORDER
The disturbance recorder function can record analog signals and binary status signals.
These signals are user configurable. The disturbance recorder function has a binary input
signal, which serves the purpose of starting the function. The conditions of starting are
defined by the user. The disturbance recorder function keeps on recording during the active
state of this signal but the total recording time is limited by the timer parameter setting. The
pre-fault time, max-fault time and post-fault time can be defined by parameters.
Содержание AQ F3 0 Series
Страница 1: ...INSTRUCTION MANUAL AQ F3x0 Feeder protection IED ...
Страница 44: ...Instruction manual AQ F3x0 Feeder protection IED 44 162 ...
Страница 84: ...Instruction manual AQ F3x0 Feeder protection IED 84 162 Figure 3 45 Polygon characteristics logic ...
Страница 148: ...Instruction manual AQ F3x0 Feeder protection IED 148 162 Figure 6 3 Panel cut out and spacing of AQ 35x IED ...
Страница 149: ...Instruction manual AQ F3x0 Feeder protection IED 149 162 Figure 6 4 Dimensions of the AQ 39x IED ...
Страница 150: ...Instruction manual AQ F3x0 Feeder protection IED 150 162 Figure 6 5 Panel cut out and spacing of the AQ 39x IED ...