9.2.1.19. Vector jump (78) ΔΑ>
Table. 9.2.1.19. - 297. Vector jump (78) technical data
Input signals
Input magnitudes
P-P voltage fundamental frequency RMS
P-E voltage fundamental frequency RMS
Monitored voltages
System any or all P-P voltage(s)
System any or all P-E voltage(s)
Chosen speci c P-P or P-E voltage
U4 voltage
Pick-up
Pick-up Δα setting
1.00…30.00 °, setting step 0.01 °
Inaccuracy
-Voltage angle
±0.15 °
Low voltage block
Pick-up setting
50.00…100.00 %Un, setting step 0.01 %Un
Inaccuracy
-Voltage
±1.5 %U
SET
or ±30 mV
Instant operation time
Alarm and trip operation time:
(Im/Iset ratio > ±0.15 ° to pick-up)
<20 ms (typical 15 ms)
Reset
Reset ratio
-Voltage angle
2.0 °
Alarm and trip reset time
<50 ms
9.2.1.20. Arc protection (50ARC/50NARC) IARC> I0ARC> (option)
Table. 9.2.1.20. - 298. Arc protection (50ARC/50NARC) technical data
Input signals
Input magnitudes
Input arc point sensors
Sample based phase current measurement
Sample based residual current measurement
S1, S2, S3, S4 (pressure and light or light only)
System frequency operating range
6.00…75.00 Hz
Pick-up
Pick-up current setting (phase current)
Pick-up current setting (residual current)
Pick-up light intensity
0.50…40.00 x In, setting step 0.01 x In
0.10…40.00 x In, setting step 0.01 x In
8000, 25000 or 50000 Lux (sensor selectable in order code)
Starting inaccuracy ArcI> & ArcI0>
±3% of set pick-up value > 0.5 x In setting. 5 mA < 0.5 x In setting
Point sensor detection radius
180 degrees
Operation time
Light only
-Semiconductor outputs HSO1 and HSO2
-Regular relay outputs
Typically 7 ms (3…12 ms)
Typically 10 ms (6.5…15 ms)
Light + current criteria (zone1…4)
-Semiconductor outputs HSO1 and HSO2
-Regular relay outputs
Typically 10 ms (6.5…14 ms)
Typically 14 ms (10…18 ms)
Arc BI only
-Semiconductor outputs HSO1 and HSO2
-Regular relay outputs
Typically 7 ms (2…12 ms)
Typically 10 ms (6.5…15 ms)
AQ-F255
Instruction manual
Version: 2.00
357
© Arcteq Relays Ltd