Instruction manual –AQ F210 Feeder Protection IED
67 (292
)
4.2.2
N
ON
-
DIRECTIONAL OVER CURRENT
I>
(50/51)
Overcurrent function (NOC) is used for non-directional instant- and time delayed
overcurrent/short circuit protection for various applications including feeder, filter and
machine applications of utilities and industry. The number of available instances of the
function depends of the IED model. Function measures constantly phase current
magnitudes which on the operating decisions are based. Monitored phase current
magnitudes can be selected fundamental component RMS, TRMS values (including
harmonics up to 32
nd
) or peak-to-peak values. Blocking signal and setting group selection
controls the operating characteristics of the function during normal operation.
Outputs of the function are Start Trip and Blocked signals. Setting parameters are static
inputs for the function which are changed only by user input in the setup phase of the
function. Non directional overcurrent function utilizes total of eight separate setting groups
which can be selected from one common source.
The function can be operating on instant or time delayed mode. In time delayed mode the
operation can be selected for definite time or IDMT. For IDMT operation IEC and ANSI
standard time delays are supported as well as custom parameters. Function includes CT
saturation checking which allows the function to start and operate accurately also in case
of CT saturation condition.
The operational logic consists of input magnitude processing, input magnitude selection,
saturation check, threshold comparator, block signal check, time delay characteristics and
output processing. The basic design of the protection function is 3-pole operation.
Inputs for the function are the operating mode selections, setting parameters and measured
and pre-processed current magnitudes and binary input signals. Function outputs START,
TRIP and BLOCKED signals which can be used for direct IO controlling and also for user
logic programming. The function registers its operation into 12 last time-stamped registers
and also generates general time stamped ON/OFF events to the common event buffer from
each of the three output signal. In instant operating mode the function outputs START and
TRIP events simultaneously with equivalent time stamp. Time stamp resolution is 1ms.
Function provides also cumulative counters for START, TRIP and BLOCKED events.
In the following figure is presented the simplified function block diagram of the NOC function.
Содержание AQ-F210
Страница 1: ...INSTRUCTION MANUAL AQ F210 Feeder Protection IED ...
Страница 255: ...Instruction manual AQ F210 Feeder Protection IED 255 292 Figure 7 1 Connection of different sensor types ...
Страница 259: ...Instruction manual AQ F210 Feeder Protection IED 259 292 Figure 7 9 13 Panel cut out and spacing of the AQ 2xx IED ...
Страница 291: ...Instruction manual AQ F210 Feeder Protection IED 291 292 ACCESSORIES ...