Port protocols
IEC 104
Modbus/TCP
DNP3
FTP
Telnet
Data transfer rate
100 MB
System integration
Can be used for system protocols and for local programming
Table. 9.1.2.2 - 275. Rear panel system communication port B.
Port
Port media
Copper RS-485
Number of ports
1
Features
Port protocols
Modbus/RTU
IEC 103
IEC 101
DNP3
SPA
Data transfer rate
65 580 kB/s
System integration
Can be used for system protocols
9.1.2.3 CPU digital inputs
Table. 9.1.2.3 - 276. CPU model-isolated digital inputs, with thresholds defined by order code.
Rated values
Rated auxiliary voltage
265 V (AC/DC)
Nominal voltage
Order code defined: 24, 110, 220 V (AC/DC)
Pick-up threshold
Release threshold
Order code defined: 19, 90,170 V
Order code defined: 14, 65, 132 V
Scanning rate
5 ms
Settings
Pick-up delay
Software settable: 0…1800 s
Polarity
Software settable: Normally On/Normally Off
Current drain
2 mA
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013