Angle measurement inaccuracy
±0.2 degrees (15…300 V)
±1.5 degrees (1…15 V)
Voltage measurement bandwidth (freq.)
7…75 Hz fundamental, up to the 31
st
harmonic voltage
Terminal block connection
Terminal block
Phoenix Contact PC 5/8-STCL1-7.62
Solid or stranded wire
Maximum wire diameter
6 mm
2
Input impedance
24.5…24.6 M
Ω
Burder (50/60 Hz)
<0.02 VA
Thermal withstand
630 V
RMS
(continuous)
NO
NOTE!
TE!
Voltage measurement accuracy has been verified with 50/60 Hz.
The amplitude difference is 0.2 % and the angle difference is 0.5 degrees higher at 16.67 Hz and other
frequencies.
9.1.1.3 Power and energy measurement
Table. 9.1.1.3 - 269. Power and energy measurement accuracy.
Power measurements (P, Q, S)
Frequency range
6…75 Hz
Inaccuracy
0.3 % <1.2 × I
N
or 3 VA of secondary
1.0 % >1.2 × I
N
or 3 VA of secondary
Energy measurement
Frequency range
6…75 Hz
Energy and power metering inaccuracy
0.5 S (50/60Hz) as standard
9.1.1.4 Frequency measurement
Table. 9.1.1.4 - 270. Frequency measurement accuracy.
Frequency measurement performance
Frequency measuring range
6…75 Hz fundamental, up to the 31
st
harmonic current or voltage
Inaccuracy
10 mHz
9.1.2 CPU & Power supply
9.1.2.1 Auxiliary voltage
Table. 9.1.2.1 - 271. Power supply model A
Rated values
Rated auxiliary voltage
85…265 V (AC/DC)
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
391
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...