Table. 5.4.8 - 206. Event codes.
Event number
Event channel
Event block name
Event code
Description
384
6
PCS
0
Switch 1 ON
385
6
PCS
1
Switch 1 OFF
386
6
PCS
2
Switch 2 ON
387
6
PCS
3
Switch 2 OFF
388
6
PCS
4
Switch 3 ON
389
6
PCS
5
Switch 3 OFF
390
6
PCS
6
Switch 4 ON
391
6
PCS
7
Switch 4 OFF
392
6
PCS
8
Switch 5 ON
393
6
PCS
9
Switch 5 OFF
5.4.9 Analog input scaling curves
Sometimes when measuring with RTD inputs, milliampere inputs and digital inputs the measurement
might be inaccurate because the signal coming from the source is inaccurate. One common example
of this is tap changer location indication signal not changing linearly from step to step. If the output
difference between the steps are not equal to each other, measuring the incoming signal accurately is
not enough. "Analog input scaling curves" menu can be used to take these inaccuracies into account.
Analog input scaling curve settings can be found at
Measurement
→
AI(mA, DI volt) scaling menu.
Currently following measurements can be scaled with analog input scaling curves:
• RTD inputs and mA inputs in "RTD & mA input" option cards
• mA inputs in "mA output & mA input" option cards
• Digital input voltages
Table. 5.4.9 - 207. Main settings (input channel).
Name
Range
Step
Default
Description
Analog input
scaling
0: Disabled
1: Activated
-
0:
Disabled Enables and disables the input.
Scaling curve 1...4
0: Disabled
1: Activated
-
0:
Disabled
Enables and disables the scaling curve and the input
measurement.
Curve 1...4 input
signal select
0: S7 mA Input
1: S8 mA Input
2: S15 mA Input
3: S16 mA Input
4: DI1 Voltage
...
23: DI20 Voltage
24: RTD S1
Resistance
...
39: RTD S16
Resistance
40: mA In 1 (I
card 1)
41: mA In 2 (I
card 2)
-
0: S7
mA
Input
Defines the measurement used by scaling curve.
Curve 1...4 input
signal filtering
0: No
1: Yes
-
0: No
Enables calculation of the average of received signal.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
© Arcteq Relays Ltd
IM00013
311
Содержание AQ F205
Страница 1: ...AQ F205 Feeder protection IED Instruction manual ...
Страница 2: ......
Страница 379: ...Figure 7 4 245 Example block scheme A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 377 ...
Страница 389: ...Figure 8 7 254 Device installation A AQ Q F205 F205 Instruction manual Version 2 04 Arcteq Relays Ltd IM00013 387 ...