5.3.7. Neutral overvoltage (U0>; 59N)
The neutral overvoltage function is used for non-directional earth fault alarms. Each device with a
voltage protection module has four (4) stages available in the function. The function constantly
measures phase-to-ground voltage magnitudes and calculates the zero sequence component. The
neutral overvoltage protection is scaled to the level of line-to-line fundamental frequency. If the line-to-
line voltage of the system is 100 V in the secondary side, the earth fault is 100% of the
U
n
when the
calculated zero sequence voltage reaches V = 57.74 V.
The formula for symmetric component calculation (and therefore to zero sequence voltage calculation)
is presented below.
See the zero sequence calculation examples below.
Figure. 5.3.7. - 59. Normal situation.
Figure. 5.3.7. - 60. Earth fault in an isolated network.
Figure. 5.3.7. - 61. Close distance short-circuit between phases 1 and 3.
The U< function is also capable of using measured neutral voltage. If the line-to-line voltage of the
system is 100 V in the secondary side, the earth fault is 100% of the
U
n
when the measured neutral
voltage is 100 V (see picture below).
AQ-E215
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
88
Содержание AQ-E215
Страница 1: ...AQ E215 Energy management IED Instruction manual ...
Страница 4: ...206 11 Contact and reference information AQ E215 Instruction manual Version 2 01 3 Arcteq Relays Ltd ...
Страница 186: ...Figure 8 13 113 Device installation AQ E215 Instruction manual Version 2 01 185 Arcteq Relays Ltd ...
Страница 206: ... Pt100 1000 Balco500 Ni power module AQ E215 Instruction manual Version 2 01 205 Arcteq Relays Ltd ...