9. Technical data
9.1. Hardware
9.1.1. Measurements
9.1.1.1. Current measurement
Table. 9.1.1.1. - 147. Current measurement module
Phase current inputs (A, B, C)
Rated current In
5A (con gurable 0.2A…10A)
Thermal withstand
30A continuous
100A for 10s
500A for 1s
1250A for 0.01s
Frequency measurement range
from 6Hz to 75Hz fundamental, up to 31st harmonic current
Current measurement range
25mA…250A(rms)
Current measurement inaccuracy
0.005xIn…4xIn < ±0.5% or < ±15mA
4xIn…20xIn < ±0.5%
20xIn…50xIn < ±1.0%
Angle measurement inaccuracy
< ±0.2 ° (I > 0.1A)
< ±1.0 ° (I
≤
0.1A)
Burden (50Hz/60Hz)
<0.1VA
Transient overreach
<8%
Coarse residual current input (I01)
Rated current In
1A (con gurable 0.2A…10A)
Thermal withstand
25A continuous
100A for 10s
500A for 1s
1250A for 0.01s
Frequency measurement range
from 6Hz to 75Hz fundamental, up to 31st harmonic current
Current measurement range
5mA…150A(rms)
Current measurement inaccuracy
0.002xIn…10xIn < ±0.5% or < ±3mA
10xIn…150xIn < ±0.5%
Angle measurement inaccuracy
< ±0.2 ° (I > 0.05A)
< ±1.0 ° (I
≤
0.05A)
Burden (50Hz/60Hz)
<0.1VA
Transient overreach
<5%
Fine residual current input (I02)
Rated current In
0.2A (con gurable 0.2A…10A)
AQ-T216
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
264
Содержание AQ 200 Series
Страница 1: ...AQ T216 Transformer protection IED Instruction manual ...
Страница 243: ...Figure 7 1 162 AQ T216 variant with binary input modules AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 242 ...
Страница 264: ...Figure 8 11 184 Panel cut out and spacing of the IED AQ T216 Instruction manual Version 2 00 263 Arcteq Relays Ltd ...
Страница 284: ...10 Ordering information AQ T216 Instruction manual Version 2 00 283 Arcteq Relays Ltd ...
Страница 285: ...AQ T216 Instruction manual Version 2 00 Arcteq Relays Ltd 284 ...