11.7 System failure relay
Table. 11.7 - 14. Technical data for the system failure relay (SF).
Number of SF relays
1
Rated voltage
250 V AC/DC
Carry:
- continuous carry
- make-and-carry for 3 s
- make-and-carry for 0.5 s
5 A
16 A
30 A
Breaking capacity DC*
40 W (0.36 A at 110 V DC)
Contact material
AgNi 90/10
*) When the time constant L/R = 40 ms.
11.8 Sensors
AQ-01 point sensor
Table. 11.8 - 15. Technical data for the AQ-01 light point sensor.
Light intensity threshold
8,000 lux
25,000 lux
50,000 lux
Detection radius
180º
Mechanical protection
IP 20
Sensor cable specification
Shielded twisted pair 0.75 mm
2
(AWG: 18)
Maximum sensor cable length (per channel)
200 m
Operating temperature
–20…+85 ºC
AQ-02 point sensor
Table. 11.8 - 16. Technical data for the AQ-02 light and pressure point sensor.
Light intensity threshold
8,000 lux
25,000 lux
50,000 lux
Pressure threshold (fixed)
0.2 bar above ambient pressure
Pressure measuring accuracy
±1.8 % (of full scale)
Detection radius
180º
Mechanical protection
IP 20
Sensor cable specification
Shielded twisted pair 0.75 mm
2
(AWG: 18)
Maximum sensor cable length (per channel)
200 m
Operating temperature
–20…+85 ºC
A
AQ
Q-101 (A
-101 (AQ
Q-101D
-101D))
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
IM00006
39