S1—S4
(amber)
Normal status.
Light information has
activated the sensor
channel.
There is a loose
connection or a system
setup has not been
performed; or
or, pressure
information has activated
the sensor channel in
question (when using
an AQ-02 point sensor).
Check the sensor wire
connection or perform a
system setup (see the
"System setup" chapter);
or
or, check what activated
the sensor.
S5
(amber)
Normal status.
The fiber sensor channel
has been activated.
There is a loose fiber
sensor connection or a
system setup has not
been performed.
Check the sensor wire
continuity or perform a
system setup (see the
"System setup" chapter);
or
or, check what activated
the sensor.
BI1–BI2
(amber)
Normal status.
The binary input has
been activated.
The binary input has a
loose connection.
Check the binary input
wiring.
BO1
(amber)
Normal status.
The binary output has
been activated.
(N/A)
—
4.3 Push button (SET)
The unit contains one push button, SET
SET, and it can be used for all operational functions. The push
button is used for setting up the system (also known as auto-configuration), for resetting the indicator
LEDs and the latched output relays, as well as for checking the input connection.
Figure. 4.3 - 7. The "SET" push button on the device's front panel.
4.3.1 System setup (auto-configuration)
After all sensors and binary lines have been connected, a system setup procedure (also known as
auto-configuration) must be performed. The sequence is initialized by pressing the SET
SET push button for
two seconds. This causes the sensor and binary LEDs to start blinking. The unit scans these inputs to
see if they are connected; when an input is detected, the corresponding LED lights up to mark that a
connection was found. All inputs that are not connected continue to blink for three more seconds.
Then, all LEDs are turned off. Additionally, the DIP switch setting are stored in the non-volatile memory
during this sequence.
All sensor inputs remain operational even when they have not been auto-configured. System setup is
only used for self-supervision purposes.