This appliance is tested and certified to the following USA and Canadian gas appliance
standards.
- ANSI Z21.88b-2003/CSA 2.33b-2003 Vented Gas Fireplace Heaters
- CAN/CGA-2.17-M91, Gas-Fired Appliances for Use at High Altitudes
Please contact Archgard Industries Ltd., if you have any questions regarding the certification of
this appliance.
APPLIANCE CERTIFICATION
INSTALLATION CODES
This appliance must be installed by a qualified gas appliance installer. The installation must
conform with the local codes or, in the absence of local codes, with the current National Fuel
Gas Code ANSI Z223.1/ NFPA 54 in the US, or Installation Code CAN/CGA-B149.1 in
Canada. Electrical connections and grounding must conform with local code, or current
National Electrical code ANSI/NFPA No. 70-1987 in the US, and in Canada the current
Canadian Electrical Code CSA C22.1.
We recommend that our gas hearth products be installed and serviced by professionals
who are certified in the U.S. by the National Fireplace Institute
®
(NFI) as NFI Gas
Specialists.
SPECIFICATIONS
Natural Gas (NG)
Propane (LP)
Manifold Pressure
1.7-3.5 in. W.C. (0.4-0.9 kPa)
6.3-10.0 in. W.C. (1.6-2.5 kPa)
Min. Supply Pressure
Max Supply Pressure
4.5 in. W.C. (1.2 kPa)
14.0 in. W.C. (3.5 kPa)
11.0 in. W.C. (2.8 kPa)
14.0 in. W.C. (3.5 kPa)
Orifice Size
#34 DMS (2.8 mm dia)
#51 DMS (1.72 mm dia)
Nominal Input Rating
23,000 - 34,000 BTU/hr (6.6- 9.8kW) 26,000 - 34,000 BTU/hr (7.5 -9.8kW)
Electrical Rating
120 VAC, 60Hz less than 2 A. /
120 VAC, 60Hz less than 2 A. /
Gas Control
ROBERTSHAW 7000 MVRB
ROBERTSHAW 7000 MVRB
Altitude
0 - 4,500 ft. (0 - 1372 M)
0 - 4,500 ft. (0 - 1372 M)
Primary Air Opening
¼” (6 mm) OPEN
FULLY OPEN
HIGH ALTITUDE INSTALLATION
When installing this appliance beyond 4500 ft. (1372 M) above sea level, the appliance must
be properly de-rated and installed according to local codes, in the absence of local codes, with
the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the US or Installation Code,
CAN/CGA-B149, in Canada.