INSTALLATION INSTRUCTIONS
Cont...
9
VENTING
Cont...
•
Chart is for one 90° bend, with 1/4” vertical raise minimum per foot of horizontal length.
•
For each additional 90° or two 45°, add 1ft of vertical height.
•
Maximum two 90º bends, or equivalent.
•
Minimum 2 ft straight length between bends.
Maintain a minimum of 1” clearance to combustibles on sides and bottom and 2” from top surface
of the vent.
The gas fireplace is designed and optimized for majority of the installations with short vents. With
taller vents the efficiency and flame characteristics will change. Therefore, an exhaust restrictor
plate is provided by the manufacturer to preserve as much of the original short vent performances as
possible on taller vent configurations.
NOTE: Maximum vent lengths subject to local codes.
VENTING CHART (FOR TOP VENTED APPLIANCES ONLY)
10 ft
36”
3 ft
1 ft
15 ft
HORIZONTAL LENGTH
(from center of flue outlet to base of termination)
V
E
RTIC
AL HEIG
HT
(from
botto
m
of
applia
nc
e to ce
nte
r of
term
ination)
7 ft
Venting in this area requires a vent restrictor plate #1.
5 ft
7 ft
9 ft
11 ft
13 ft
30”
H
eater
Maximum Hori-
zontal run for
Rear Vent is 20”
from the back of
the unit to termi-
nation or 16” with
a 45
0
elbow.
VERTICAL VENTING (THROUGH THE ROOF) FOR ROOFTOP VENTED APPLIANCES
•
Use only Simpson Duravent 4 x 6-5/8” direct vent systems and Simpson Duravent venting compo-
nents.
•
Maximum vertical height of 25 feet.
•
Vertical height of the vent system must have at least 3 ft or more per 90
0
elbow in the vent system.
•
Vertical height of the vent system must also be increased 1 ft for every 2 ft of horizontal length
added to the vent system.
Example:
A vertical venting system with a 90
0
elbow, a horizontal offset of 4 ft and another 90
0
elbow.
Vertical height of the vent system must be 3ft + 2ft + 3ft = 8ft or higher to a maximum of 25 ft.
Vertical Venting between 10 ft and maximum 25 ft requires restrictor plate #2