15
FULL LINER INSTALLATION
There are different ways of installing a full liner, you can drop it in from the top or bring it up from
the bottom.
In the USA, in order to meet the requirements of UL 1777, you may have to insulate your liner and
if you do, it will have to be done as a system to manufacturers certified installation instructions.
In Canada, you can run ULC S635 or ULC S640 liner systems. If you would like to obtain a sys-
tem with certified reduced clearances, there are manufacturers who have tested their ULC S640
liners for close clearance and even zero clearance to combustibles using their own insulation/
installation requirements which must be adhered to. As Archgard has no control over what liner
system is being used with the CHALET 1800 WOOD Fireplace Insert, here we can only give a
general overview of the installation procedure of dropping a generic uninsulated liner from the top
of the chimney and connecting it to the flue collar of the appliance.
It is of the utmost impor-
tance that the installation instructions of the liner system that you will be using be con-
sulted when doing your installation.
1. If you will be doing any modifications to the damper assembly or to the back wall or smoke
shelf (first check if you are allowed to do so), to accommodate the liner, now would be a good
time to so and to fasten the permanent warning label, that comes with the insert, to the back
wall of the fireplace warning future owners that the fire-
place may have been altered to do this installation, in
the event that the insert is ever removed.
2. Drop the liner down from the top of the chimney. If it is
a tight fit or if offsets are present, you may have to at-
tach a cone to the end of the liner with some rope com-
ing out the end of it or just squeezing the ends of the
liner together and duct taping some rope to the end it.
Drop the rope down and with someone at the bottom
pulling on the rope and someone at the top pushing on
the liner, it should get to the bottom.
3. When it gets past the smoke shelf (you may have prob-
lems getting the liner past this point, you may have to
order an ovalized liner or you may wish to ovalize a
section of liner yourself. If you ovalize it yourself, check
with the liner manufacturer to see if they will honor any
warrantees if
you
ovalize the liner. If you aren’t careful
or don’t have the equipment, you could damage the
liner when you ovalize it), if you squeezed the ends of
the liner, cut the damaged ends off with a knife and tin
snips. If an adapter is being used, rivet it onto the flex
liner now. Rivets work better on thin liner because
screws tend to work their way out (loosen out) but if
you use rivets, make sure you use rivets that are
marked SSSS for Stainless Steel Shank and Stainless
Steel Rivet. If you use rivets that just say SS then all
you are getting is a Steel Shank and Steel Rivet and they will corrode in a short time.
NOTE:
a) masonry or steel shall not be removed from the fireplace to accommodate the appli-
ance; (b) masonry or steel, including the damper plate, may be removed from the smoke shelf
and adjacent damper frame if necessary to accommodate a flue liner, provided that their removal
will not weaken the structure of the fireplace and chimney and will not reduce protection to com-
bustible materials.