20
Installation
13.0 Venting Instructions
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result
in carbon monoxide (CO) poisoning and possible death. The appliance must not be connected to a chimney flue serving a
separate solid fuel burning appliance.
CAUTION
Only approved 3” (76mm) double wall aluminum or stainless flex liners and approved vent terminals are to be used for this appliance.
This appliance is designed for dual 3” (76 mm) double wall aluminum flex liner. The liner must run the entire length of the chimney from
the appliance to the termination.
The flue length must be a minimum of 10’ (3.05 M) and a maximum of 40’ (12.2 M) from the top of the gas fireplace insert.
Masonry chimneys may take various contours which the flexible liner will accommodate, however, keep the flexible liner as straight as
possible, avoiding unnecessary bending but at all times keep a minimum of 3” (76 mm) inside bend radius.
The Air Intake Flex Liner must form a tight connection to the inlet air collars of the termination cap and the appliance.
The Exhaust Flex Liner must form a tight connection to the exhaust collars of the termination cap and the appliance.
The Air intake and Exhaust connections are marked on the gas appliance. See Figure 13.1.01.
DO NOT REVERSE THESE CONNECTIONS
CAUTION
To ensure that the venting is not accidentally obstructed or punctured, the damper of the host fireplace must be permanently
disabled by either complete removal of the damper, or by being fully blocked open, for the installation of a gas fireplace insert.
Figure 13.0.01
: Intake & Exhaust as viewed from top of fireplace.
Intake
Exhaust
DO NOT USE SILICONE TO SEAL VENT