18
Installation
Using a Co-linear to Coaxial Adapter
Front view of
DV Insert
Exhaust
Fresh air intake
Termination
Roof Flashing
3” (76 mm) Flex Liner
Sealed Flashing
Coaxial pipe
( min. 4” exhaust - 6 5/8” Intake)
Colinear to coaxial adaptor
Blown Insulation
Blown Insulation
Max. 6 ft or
50% of the
total vent
run, which
ever is shorter
Min. 18”
Min 10 ft
Ceiling
Roof
Must maintain 1”
form coaxial pipe
to insulation and
combustible
The gas fireplace can be converted from co-linear to coaxial when it is desired to remove a section of the masonry fireplace chimney to
below the roof line.
WARNING
This appliance must be installed by a qualified gas appliance installer. The installation must conform with the local codes or, in
the absence of local codes, with the current National Fuel Gas Code ANSI Z223.1/ NFPA 54 in the US, or Installation Code CAN/
CGA-B149.1 in Canada. Electrical connections and grounding must conform with local code, or current National Electrical code
ANSI/NFPA No. 70-1987 in the US, and in Canada the current Canadian Electrical Code CSA C22.1.
•
The sections of coaxial pipe
cannot be longer than 6ft. or 50%
of the total vent length, whicever
is shorter
•
A sealed flashing must be placed
on top of the chimney where the
co-linear to coaxial adapter is
seated
•
The total vent run must be a
minimum of 10ft. from the top of
the gas fireplace insert
•
A 1" clearance must be maintained
from the coaxial pipe to insulation
and combustible material
•
The termination must be 18"
from the roof to the bottom of the
termination
Co-linear to coaxial adapter