11
Installation
Hearth Clearances
Non Combustible
Zone
16”
Non Combustible
Zone
16”
31 3/4”
TOP VIEW
LEFT SIDE VIEW
The Non Combustible
Zone may contain any
noncombustible material or
open air space. Never use
combustible materials within
the Non Combustible Zone.
Non Combustible Zone
16"
(406.4 mm)
16"
(406.4 mm)
7"
(178 mm)
28-3/4"
(730.25 mm)
WARNING
Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance
may result in property damage or personal injury. All specified clearances must be maintained from the top surface of carpeting, tile,
etc.
Combustible Zone
NOTE
All specified clearances must be maintained from the top surface of carpeting, tile, etc.
Any hearth that extends outward in front of the insert must not have any combustible material closer than 7" (178 mm) to the bottom
of the gas fireplace insert regardless of whether a noncombustible material covers the combustible material. This includes any type of
framing underneath a noncombustible material such as tile, marble, or stone. Any material farther than 7" (178 mm) to the bottom or 16"
(406 mm) from the front of the door of the gas fireplace insert can be combustible.