A.3.29
Phase Mode, Set (PHM)
Command:
mdPHM
Starts single or 3 phase measurement mode.
m
Mode
d
Mode
0
1ph, 2 wire, single phase
0
Tabular Display
(with Power)
1
1ph, 3 wire, 2 element,
split phase
1
Tabular Display
(with Energy)
2
3ph, 3 wire, 2 element
2
Vector Diagram
3
3ph, 3 wire, 3 element
3
Voltage & Current
Sequence
4
3ph, 4 wire, 3 element
4
Voltage Sequence
5
3ph, 4 wire, 2.5 element
5
Current Sequence
A.3.30
Phase, Return (PHS)
Command:
PHS
Returns the phase angle of Channel 2 relative to Channel 1. Use the #SPH
command to set the phase preference: 0 – 360 or
±
180 degrees, leading
or lagging. In 3-phase mode, returns the average of the individual phase
measurements.
Response: Numeric ASCII string.
A.3.31
Power, Return (PWR)
Command:
#PWR
Returns the active power of Channel 1 and 2 together. Channel 1 must be
set to measure AC voltage and Channel 2 AC current. In 3-phase mode,
it returns the total active power. When “1” precedes the PWR command,
it replaces Power Quantities with Energy Readings.
Response: Numeric ASCII string.