Terminal Connection Details
Turning the screw clockwise tightens, and counterclockwise loosens, the
terminal connector screws. Screws are tightened completely clockwise
when leaving the factory.
Before inserting wire, make sure to turn
the necessary connector screws counterclockwise to fully open the
connector jaw, then turn clockwise to tighten
.
6.4.4
Sealing Cable Port Specifications
Standard configuration includes a weather-resistant, sealing cable port
for wiring all signals and power to and from the Model 1095A/C. Multi-
conductor cable can be sized so that the sealing cable port will seal
when tightened. One such cable that works is Belden 9747, audio,
control and instrumentation cable. Belden 9747 has 12 pairs of 22 AWG
stranded wire with PVC insulation and a PVC jacket. The nominal outer
diameter is 0.425 inches.
Figure 6.1: Sealing Cable Port
Selected Sealing Cable Port Specifications
Cable Range 1 (Standard)
6 mm to 12 mm (0.24 in to 0.47 in)
Cable Range 2 (Optional)
5 mm to 9 mm (0.20 in to 0.35 in)
Thread Size & Type
1/2 in NPT
Clearance Hole
20.3 mm (0.80 in)
Degree of Protection
IP65
60