VP5000-DC/DC60, VP5000-DC/DC200-HL
Product description
Last edited 2019-02-08
by Sonja Scheunert
Filename
VP5000_DCDC60_200-HL_installation_manual_v1-4en.docx
27 / 173
VECTOPOWER
VP5000-DC/DC60
VECTOPOWER
VP5000-DC/DC200-HL
Max. positive / negative
current at the output side
[/-], peak for 30
seconds
Condition: no current
before the peak.
150 A DC at 650 V DC in the DC link
[DC+/-], 30 l/min / 8 gpm coolant at
35 °C / 95 °F and 45 °C / 113 °F
ambient temperature
480 A DC at 650 V DC in the DC link
[DC+/-], 30 l/min / 8 gpm coolant at
35 °C / 95 °F and 45 °C / 113 °F
ambient temperature
Max. continuous power on
the output side [/-
]
60 kW
200 kW
Maximum peak power on
the output side [/-
]
81.8 kW
240 kW
Current ripple on the output
side
[/-]
Depending on input and output values
Depending on the external network in the DC link [DC+/-] and on the output
side [/-].
See chapter 3.3.4 Product description, Technical data, Electrical data - voltage
ripple
Voltage ripple on the output
side
[/-]
Current ripple on the DC
link side
[DC+/-]
Voltage ripple on the DC
link side
[DC+/-]
Table 5: Electrical values for operation as a buck converter
3.3.3
Electrical data for operation as a boost converter
For operation as a boost converter, it must be checked whether a ballast is required for the
VECTOPOWER VP5000-DC/DC60.
VECTOPOWER
VP5000-DC/DC60
VECTOPOWER
VP5000-DC/DC200-HL
Minimum DC link voltage
[DC+/-]
Rule: 110% of the actual voltage at
[/-], but at least +20 V DC
above the actual voltage at
[/-]
[/-] 48 V DC to 199 V DC ->
plus 20 V DC
Example: [/-] 80 V DC +
20 V DC = [DC+/-] 100 V DC
[/-] 200 V DC to 720 V DC -
Actual voltage at [/-]
+20 V DC
Example: [/-] 28 V DC +
20 V DC = [DC+/-] 48 V DC