CHECK YOUR WATER PRESSURE AND PUMPING RATE 

 
Two water system conditions must be checked carefully to avoid unsatisfactory operation or equipment damage: 
 

1.

 

Minimum water pressure required at the filter tank inlet is 25 psi. If pressure is over 50 psi, a pressure reducing valve must 
be installed in the water supply line ahead of the hydro-charger (Fig. 1, 2 or 3). 

 

2.

 

The  pumping  rate  of  your  well  pump  must  be  at  least  5  gallons  per  minute  (gpm)  for  satisfactory  operation  of  the 
aircharger.  In  addition,  the  pumping  rate  must  equal  the  required  backwash  flow  rate  of  your  model  (see  below  for 
backwash flow rates). To measure the pumping rate of your pump, follow these instructions: 

 

a.

 

Make  certain  no  water  is  being  drawn.  Open  spigot  nearest  pressure  tank.  When  pump  starts,  close  spigot  and 
measure time (in seconds) to refill pressure tank (when pump shuts off). This figure represents cycle time. 

b.

 

With the pressure tank full, draw water into a container of known volume, and measure the number of gallons drawn 
until the pump starts again. This is draw-down. Divide this figure by cycle time and multiply the result by 60 to arrive 
at the pumping rate in gallons per minute (gpm). To aid in your calculation, insert the date in the following formula: 

 
 

DRAW-DOWN ______ 

÷ 

CYCLE TIME _______ x 60 = PUMPING RATE ________ (gals) (secs.) (gpm) 

 
 

EXAMPLE:

  CYCLE TIME is 53 seconds; DRAW-DOWN is 6 gals.; then, PUMPING RATE equals: 

 

 

6 gals. 

÷ 

53 seconds x 60 = 6.8 gpm 

 
 

See chart on page two for minimum flow rates. 

 

 

NOTE: 

If your pumping rate is inadequate, do not install your filter until problem is corrected. 

 
 

Backwash Flow Rates 

The most important criteria in sizing a filter is the capacity of the pump. The water must pass through the filter media at a service 
flow rate that allows it to operate properly.  The filter must also be backwashed at a flow rate sufficient to dislodge and remove 
captured  particulates.    Failure  to  provide  sufficient  water  will  cause  a  build-up  of  particulates  in  the  filter  media,  impairing  its 
filtration ability.  In order for your filter to backwash and rinse properly, your pump must be capable of providing the backwash 
flow rates indicated in the above specification chart. 
 

Backwash Frequency 

 

NOTE: 

Add one person if you have a dishwasher. 

 

 

How to calculate gallons of water between regenerations 

 

 

ppm of capacity between regenerations 

 

÷ ppm of iron in the water sample 

 

= number of gallons supplied between regenerations 

 

- reserve capacity (number of people x 75 gallons) 

 

 

EXAMPLE: 

6,000  

ppm between regenerations 

 

 

÷ 4  

ppm of iron - 4 is the minimum setting of compensated iron [To be entered by the user] 

 

 

= 1,500  

gallons between regenerations 

 

 

– 375  

gallons reserve capacity (5 people x 75 gallons) 

 

 

= 1,125  

GALLONS - BETWEEN REGENERATIONS 

 

 

How to calculate number of days between regenerations 

 
 
 

Содержание CAN165BM-100

Страница 1: ...nual Birm Filter Note 1 Read all instructions carefully before operation 2 Avoid pinched o rings during installation by applying provided with install kit NSF certified lubricant to all seals Rev 4 December 28 2011 ...

Страница 2: ...ications 3 How Your System Works 3 Programming 5 Sizing Requirements 6 Before Installation 8 General Installation 10 Start Up 12 Maintenance 15 Control Valve Exploded View 16 Control Valve Parts List 17 Trouble Shooting 18 Warranty 19 ...

Страница 3: ...quested by customer during a period of little or no water use The backwash cycle lasts approximately 15 minutes after which filtered water service is restored While backwashing is taking place raw water automatically bypasses the filter if required If possible avoid using water during backwashing to prevent iron laden water entering your household plumbing system This valve is controlled with simp...

Страница 4: ... GALLON SETTING If the valve is not in service it will read CANATURE while the valve returns to the service position Mixed Regeneration Option This is an option that can be used on filtration units This will enable the unit to be set for gallons between regenerations with a frequency of days as an override to ensure the media bed stays in optimal working order Control Operation During A Power Fail...

Страница 5: ...and press until you hear a beep to unlock the display screen Press or to select which setting to modify 2 To change setting press When the display flashes the value may be changed Press or to change the value Press to accept the value 3 Press to return to previous menu Figure 2 Program Flow Chart ...

Страница 6: ...ter in order to produce the regenerate solution brine for softeners for the next regeneration cycle The water is accurately measured through the valves brine line flow control to make a precise quantity of regenerant solution 13 LOAD DEFAULT L CAPA It is not recommended to use any of these options The function of this option is to load pre set values of BACKWASH BRINE RINSE and REFILL for large me...

Страница 7: ...0 PUMPING RATE ________ gals secs gpm EXAMPLE CYCLE TIME is 53 seconds DRAW DOWN is 6 gals then PUMPING RATE equals 6 gals 53 seconds x 60 6 8 gpm See chart on page two for minimum flow rates NOTE If your pumping rate is inadequate do not install your filter until problem is corrected Backwash Flow Rates The most important criteria in sizing a filter is the capacity of the pump The water must pass...

Страница 8: ... ferrous iron precipitated iron also known as red water or ferric iron and bacterial iron also known as iron bacteria There is no apparent upper limit of iron concentration for the filter but special care must be taken when selecting a filter model if your water has a combination of high iron very low pH and or manganese MANGANESE Mn The presence of manganese can be bothersome even for a chemical ...

Страница 9: ...ezing may cause permanent damage to this type of equipment and will void the factory warranty 6 Allow sufficient space around the unit for easy servicing THE IMPORTANCE OF YOUR PRESSURE TANK The pressure tank found on private well systems becomes an integral part of the filter system by providing necessary mixing and contact time to the Air Charged water While the iron filter will perform better o...

Страница 10: ...arter full of water to protect distribution during gravel installation Slowly and carefully add the gravel support bed and the filtration media leveling each layer as it is placed into the tank Unplug the riser tube carefully position the valve over it and turn the valve into the threads in the fiberglass tank tightening securely into tank Note Ensure that the internal O ring in the valve fits sec...

Страница 11: ...o the control valve as damage may result to the internal parts Check to be certain water supply pipe is connected to the control valve inlet fitting and pipe connected to control valve outlet fitting is in direction of house service 7 Perform all plumbing according to local plumbing codes 8 Use a minimum pipe or tubing size for the drain line not to exceed 10 ft 3M 9 Use a pipe or tubing for backw...

Страница 12: ...1 Plug the valve into an approved power source 2 When power is supplied to the control the screen may display INITIALIZING WAIT PLEASE while it finds the service position 3 If the system has been inactive you may have to hold and press until you hear a beep to unlock the display screen Press and hold for 3 seconds to initiate a manual regeneration and advance the valve to the Backwash position Ope...

Страница 13: ... and proceed with the filter installation During the time required to install the filter system the iron fouled softener resin will be chemically cleaned 4 After the filter installation is completed and final adjustments have been made turn the water back on to the softener reconnect the brine draw tube then reposition the timer on the softener to the backwash position Allow the timer to perform a...

Страница 14: ... regenerations should be performed when little or no water will be used in the household New Sounds You may notice new sounds as your water filter operates The regeneration cycle lasts approximately 1 2 hour During this time you may hear water running intermittently to the drain Manual Bypass In the case of emergency you can isolate your water filter from the water supply using the bypass valve lo...

Страница 15: ...en the air charger and the pressure tank are clear and free from any obstructions Notes Original settings Pumping Rate Air draw time Pressure setting Primary switch Secondary switch Split stream only Regeneration interval _________________________________________________________________________ _________________________________________________________________________ ______________________________...

Страница 16: ...16 Control Valve Assembly Exploded View See parts listing on next page 17 ...

Страница 17: ...nnect or 1 A 26 13000426 S crew S T2 9 13 Large W af er 2 A 27 05056038 D rai n Fi t t i ng 1 A 28 26010003 O R i ng φ 18 2 65 1 A 29 05056036 D LFC B ut t on R et ai ner 1 A 30 05056079 O R i ng φ 15 0 8 1 A 31 05056143 D LFC 2 1 A 32 05056035 B LFC B ut t on R et ai ner 1 A 33 05056191 B LFC 2 1 A 34 05056138 O R i ng φ 14 1 8 1 A 35 05056100B B LFC Fi t t i ng 1 A 36 05056106 B ri ne Li ne S cr...

Страница 18: ...ar from filter tank Contact dealer for proper location of Air injector and pressure tank 5 Solenoid valve malfunction or inadequate supply system pressure flow rate Replace solenoid valve check specs for proper pressure flow rates 1 Filter bed overloaded with precipitated iron See problem above 2 Control inlet outlet valve s not fully open Open valves 3 Sand silt or mud collecting in filter bed Ch...

Страница 19: ...om the date thereof Ten Year Guarantee on Mineral Tanks and Brine Tanks Canature North America Inc will provide a replacement mineral tank or brine tank to any original equipment purchaser in possession of a tank that fails within 120 months provided that the water conditioner is at all times operated in accordance with specifications and not subject to freezing Exceptions Canature North America I...

Отзывы: