AQUAMAXX TWIN 1200L Скачать руководство пользователя страница 1

TWIN 800L & 1200L

AQUAMAXX VARIABLE SPEED BOOSTER SET

OPERATING & MAINTENANCE MANUAL

Содержание TWIN 1200L

Страница 1: ...TWIN 800L 1200L AQUAMAXX VARIABLE SPEED BOOSTER SET OPERATING MAINTENANCE MANUAL ...

Страница 2: ...ved The AquaMaxx set is designed to start automatically Make hydraulic connections and to prime the pumps before making any electrical connections The connection of the control panels must be performed by a qualified electrician in accordance with the present electrical standards The AquaMaxx set and control panels must be connected to an efficient earthing system first prior to any other electric...

Страница 3: ...anifolds threaded Ball valves WRAS approved on discharge of each pump Check valve included for each inverter with flow passage Pressure vessel WRAS approved Electrical section Flow passage Inverter module on the discharge line of each pump The FLOW PASSAGE INVERTER system is a device installed in line with the pump s discharge outlet It includes a pressure sensor a flow sensor and an electronic in...

Страница 4: ...his manual aims to provide information and instructions essential to adequately perform all activities related to the use of the product purchased This manual and documentation are intended to be viewed by all persons involved in the life cycle of the AquaMaxx set and therefore must be accessible to the user Compliance with all safety requirements is an obligation of the customer The following ins...

Страница 5: ...gings The individual safety standards of the country of destination should be abided by during the use of equipment READ THE INSTRUCTION MANUALS OF EVERY PUMPS MOTORS CONTROL PANELS AND OTHERWISE OF ALL COMPONENTS FOLLOW THE PROVISIONS OF THE SAFETY AND PERFORM THE PLANNED MAINTENANCE RECOMMENDED IN THE INSTRUCTION MANUALS Danger Risk of electric shock Warning The AquaMaxx set must be fitted in a ...

Страница 6: ...adius Reassembly Installation of the AquaMaxx set must be performed by skilled and authorised installers During installation apply all safety behaviours issued by the competent bodies and suggested by common sense Install the unit in a dry well ventilated place Rest the unit on a flat regular and solid surface The unit can only be installed in the horizontal position REASSEMBLY PROCEDURE TWIN PUMP...

Страница 7: ...ly Un pack the controller s manifold system and mount vertically and tighten the unions back up A 2L Vessel and T Piece are supplied loose and is to be fitted to the discharge line TWIN 800L 1200L 20mm gland for incoming power cable into the junction box Power up the AquaMaxx Set and follow the standard set up process ...

Страница 8: ...to be connected during assembly and the last to be disconnected during disassembly The installation of a differential switch is recommended whose nominal functioning differential current does not exceed 30 mA use highly sensitive differential circuit breakers 30 mA in Class A or AS For AquaMaxx sets with single phase power supply versions M T connect power supply directly to the inverter as follow...

Страница 9: ...hase for electric a c single phase and three phase motors It keeps the system pressure constant at a value defined by the user adapting pump performance to instant request changing the number of motor revs It carries out continuous controls on electric and functioning parameters saving the pumping unit from all common anomalies over currents dry running etc It works in stand alone configuration or...

Страница 10: ...y on controller defined as Master The controller defined Slave will receives automatically settings from the controller defined Master If master E SERIES is turned off the slave E SERIES works in a stand alone mode For the settings of the E SERIES please refer to attached document Before removing the inverter cover or starting an investigation on the equipment the system must be disconnected from ...

Страница 11: ...if the pressure detected is less than the predetermined threshold you can put the group OUT OF SERVICE prior to the automatic start up by hitting START STOP Where the E SERIES was OFF when the last shut down occurred the group will remain OUT OF SERVICE following the 10 second start phase To start up hit START STOP and confirm In parallel inverter installations the MASTER inverter fully controls t...

Страница 12: ...ed speed systems a large vessel reservoir is not required The vessel air charge should be maintained at 0 7 bar below the systems nominal operating pressure e g Target System Pressure 5 0 bar Vessel Air Pressure 4 3 bar Inverter Settings See attached E SERIES operating maintenance manual Pump Details See attached operating maintenance manual TWIN 800L 1200L ...

Страница 13: ...Typical installation example TWIN 800L 1200L ...

Страница 14: ...if a specific flow rate and pressure is required we would recommend you check with your supplier to ensure the AquaMaxx will meet the demand efficiently TWIN 800L 1200L ...

Страница 15: ...NOTES ...

Страница 16: ...Direct Pumps and Tanks Ltd Unit 12 Soloman Road Cossall Industrial Estate Ilkeston Derbyshire DE7 5UA 01159 444474 info dpandt co uk ...