Environmental Monitoring System (EMS-5 / 10) Instruction Manual
23
5
Maintenance
Ensure you have read the Safety Information in
Section 1
before undertaking maintenance.
5.1
Cleaning
✓
Clean the outside of the unit. Use a dry,
clean cloth.
DO NOT
use abrasive agents or solvents to
clean the equipment.
5.2
Troubleshooting
The table below lists the most common problems and their solutions. If a problem cannot be solved then please
call support on
+44 (0)1249 715698
or visit our website at
Problem
Possible Cause
Possible Solution
System does not power on
Power
cable
is
incorrectly
connected to the Master Panel.
Check the power cable. Review
section
Switched fused spur
is faulty or
inactive.
Check fuses and power on the
switched fuse spur. Review
section
3.1.2.
Sensor data is intermittent
or inactive
Sensors not connected properly.
Check Leader Cable and connections.
Review
section 3.2.2.
Leak detected but no leak
present
Sensor cable is touching something
conductive.
Check Leader Cable and connections.
Review
section 3.2.2.
Sensor cable is over 100 metres in
length.
Sensor cable had debris on it.
Clean sensor cable.
EMS disabled with power
LED flashing every 10
seconds and sounder
activating every 2 seconds
Communications loss between EMS
motherboard and interface board.
Contact Aqualeak if unable to restore
communications.
EMS disabled with power
LED off and sounder
activating every 1 second
Communications loss between EMS
motherboard and front panel.
Contact Aqualeak if unable to restore
communications. Otherwise, where
restored, the EMS will automatically
reset after a maximum of 60 seconds.
Table 9:
Troubleshooting