AQUAHEAT HEAT PUMP 

OPERATING MANUAL 

 

TF200/3 

PC8001 Controller

 

 

Содержание TF200/3

Страница 1: ...Ref 01 Page 1 of 11 Contact number 0861 50 35 50 AQUAHEAT HEAT PUMP OPERATING MANUAL TF200 3 PC8001 Controller ...

Страница 2: ...ce HELP Press this button to check button function or system state MODE Press this button to change the current mode page up or confirm current operation enter or save CLOCK Press the button to set the clock the timer on or timer off UP Press this key to select the upward option or increase the parameter value DOWN Press this key to select the downward option or decrease the parameter value ...

Страница 3: ...enter system Press twice TEMPERATURE Press to enter press to see temperature press to go back SWITCH Press press to enter to see switch press to go back Default Switch 1 CL 8 OP 2 CL 9 CL 3 CL 10 OP 4 OP 11 CL 5 CL 12 CL 6 CL 13 CL 7 CL 14 OP OUTPUT Press press to enter to see output press to go back Default Output 1 ON 9 OFF 2 ON 10 OFF 3 ON 11 OFF 4 OFF 12 35 ON 5 ON 13 35 ON 6 OFF 14 35 ON 7 ON...

Страница 4: ... No 04 System 4 HP NO 20 Device 2 probe No 05 System 1 LP Yes 21 Device 3 probe No 06 System 2 LP Yes 22 Device 4 probe No 07 System 3 LP Yes 23 Suction 1 probe No 08 System 4 LP NO 24 Suction 2 probe No 09 Water flow Yes 25 Suction 3 probe No 10 Elc Overload NO 26 Suction 4 probe No 11 Remote ON OFF Yes 27 In Out prot Yes 12 System Protect No 28 Cooling mode Yes 13 Outlet probe Yes 29 ECO Heating...

Страница 5: ...pray se 35 00 C A 04 Deice temp 4 00 C C Compressor C 01 Min on time 120 seconds C 04 Capacity CTRL 3CA C 02 Min off time 180 seconds C 05 Rotation FIFO C 03 Comp delay 300 seconds D Defrost D 01 Start temp 7 00 C D 05 Eco min time 3M D 02 End temp 13 00 C D 06 Defrost type NOR D 03 Def cycle 45M D 07 Heater CTRL On D 04 Max duration 8M D 08 Auto set 4 00 C ...

Страница 6: ... 05 Super heat 2 5 00 C E 13 Min place 100N E 06 Init place 2 350N E 14 Defrost place 350N E 07 EEV 3 mode Auto E 15 Cooling place 350N E 08 Super heat 3 5 00 C F Fan F 01 Speed High F 06 Min Heat 20 00 C F 02 Max Cool 40 00 C F 07 Stop Heat 30 00 C F 03 Min Cool 15 00 C F 08 Min Start time 0H F 04 Stop Cool 10 00 C F 09 Min Stop time 8H F 05 Max Heat 10 00 C F 10 CTRL Probe Coil H System H 01 Res...

Страница 7: ...op filter 2 17H P 05 Filter No R Temperature R 01 Cooling set 8 00 C R 13 Elec AMB 15 00 C R 02 Heating set 27 00 C R 14 Elec delay 30M R 03 Auto set 30 00 C R 15 Elec force 5 00 C R 04 Cool diff 1 00 C R 16 Compensation No R 05 Cool stop 1 00 C R 17 Compens Max 5 00 C R 06 Heat diff 1 00 C R 18 Constant 8 00 C R 07 Heat stop 1 00 C R 19 Cool AMB 35 00 C R 08 Min cool 8 00 C R 20 Heat AMB 5 00 C R...

Страница 8: ... OFF 1 E03 28 06 2013 14 00 Compressor 3 OFF Compressor 4 OFF Fan high speed OFF Fan low speed OFF Circulate pump OFF 4 way Valve OFF Elec Heater OFF Spray valve OFF Alarm OFF PARAMETER RESET TEMP TYPE Reset the settings to factory default values Celsius degree Press to confirm Fahrenheit degree ...

Страница 9: ...Ref 01 Page 9 of 11 ...

Страница 10: ...Ref 01 Page 10 of 11 Sample images ...