Page - 93
POOL SPA SENSOR SHORT
or
POOL SPA TEMP SENSOR SHORT
ISSUE
Shorted or open water sensor.
RESOLUTION
A qualified technician should replace the water sensor. Until the sensor is replaced, the setpoint is
limited to 96° F (35.5° C)
SMART COMM FAULT
ISSUE
Heat Pump is not receiving a signal from an external controller using a smart connection point.
RESOLUTION
1. Confirm a smart external controller is being used.
l
If not, set external controller mode to "none" instead of "SMART".
o
Configure for Smart Controller
2. Confirm connection points from the external controller to the heat pump are correctly configured.
l
3. If using a smart external controller, confirm the controller is correctly set to send signals to the heat pump.
See manuals or guides provided with the external controller.
SOURCE FLOW FAULT
ISSUE
If source water flow goes on and off 5 or more times during one call for heating or cooling, the Heat
Pump will deactivate.
RESOLUTION
Confirm source water pump is operating correctly.
SOURCE-IN SENSOR SHORT
or
SOURCE-IN SENSOR OPEN
ISSUE
Shorted or open water sensor.
RESOLUTION
A qualified technician should replace the water sensor. Until the sensor is replaced, the setpoint is
limited to 96° F (35.5° C)
SOURCE-OUT SENSOR SHORT
or
SOURCE-OUT SENSOR OPEN
ISSUE
Shorted or open water sensor.
RESOLUTION
A qualified technician should replace the water sensor. Until the sensor is replaced, the setpoint is
limited to 96° F (35.5° C)
3
-
T
roubl
es
hoot
ing
Содержание SunPower SP05
Страница 2: ......
Страница 70: ...Page 66 Water Source WS10 Water Source WS03 WS05 SunPower SP05 2 Appendix ...
Страница 76: ...Page 72 l Follow all National Electric Codes NEC and or State and Local guidelines 2 Appendix ...
Страница 77: ...Page 73 2 Appendix ...
Страница 79: ...Page 75 2 10 Menu Trees 2 Appendix ...
Страница 80: ...Page 76 2 Appendix ...
Страница 107: ......
Страница 108: ......