1.4.f Adjusting Water Flow Using ΔT (Delta-T)
The Delta-T is the temperature difference between the water temperatures entering and leaving the heat pump.
The equipment can be fine-tuned for maximum performance by balancing water flow rates to maintain an
ideal ∆T.
The adjustment procedure must be completed with the unit in heating mode.
l
Installed temperature ports are required to perform the following procedures.
l
These ports are typically located on the pool in and pool out water lines approximately six inches away from the
heat pump.
PLEASE NOTE -
l
The installation of temperature ports is required for all Great Big Bopper
®
installations on
both inlet and outlet piping.
n
Temperature Port Kit (# STK0133)
Temperature Port
(Shown with Probe)
1. Adjust the thermostat to its lowest setting with the unit in
heating mode.
2. Deactivate the water filtration pump.
3. Confirm that the filters leading to the heat pump are clean.
4. Adjust the valves controlling water headed towards the heat
pump to the half-open position.
5. Adjust the valves controlling water leading away from the
heat pump to a fully open position.
6. Activate the pool water filtration pump.
7. Slowly raise the thermostat temperature until the heat pump
activates.
l
After a four-minute delay, the heat pump's compressor will start.
8. With the heat pump running, confirm the filtration pump is operating properly with adequate flow and no short
cycling.
9. Wait for water temperatures to stabilize (approximately 5 minutes).
12. Adjust valves in the following order using the temperature chart provided.
a. Adjust the valve that controls water exiting the heat pump until the correct temperature differential is
achieved. Match the temperature measured with a temperature probe to the chart.
b. Wait for water temperatures to stabilize. Then check the temperature again. Re-adjust the valve as needed.
13. Mark valves at these positions for future reference.
HEAT EXCHANGER
TYPE
MODEL
TEMPERATURE
Titanium ThermoLink
®
BB500 50 Hz 380 - 415 V
3° to 7° F
(1.7° C to 3.9° C)
Titanium ThermoLink
®
BB500 60 Hz 208 - 230 V
4° to 8° F
( 2.2° C to 4.4° C)
Titanium ThermoLink
®
BB500 60 Hz 460 V
4° to 8° F
( 2.2° C to 4.4° C)
Table 1 - Temperature Chart
1
-
Ins
ta
ll
at
ion
Содержание GBB
Страница 2: ......
Страница 25: ...Page 21 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Страница 29: ...Page 25 1 Installation...
Страница 32: ...Page 28 1 Installation...
Страница 36: ...Page 32 1 Installation...
Страница 37: ...Page 33 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Страница 41: ...Page 37 1 Installation...
Страница 43: ...Page 39 1 Installation...
Страница 46: ...Page 42 1 Installation...
Страница 50: ...Page 46 1 Installation...
Страница 53: ...Page 49 1 Installation...
Страница 55: ...Page 51 1 Installation...
Страница 74: ...Page 70 l Follow all National Electric Codes NEC and or State and Local guidelines 3 Appendix...
Страница 75: ...Page 71 3 8 Schematics Some schematics have been provided in the appendix of this manual 3 Appendix...
Страница 77: ......
Страница 78: ......