Page - 11
1.4.e Water Flow Rates
Maintain water flow rates as indicated. Please note, these specifications relate to the heat pump only. Code-
specified whole system turnover rates must be satisfied.
NOTICE
Failure to heed the following may result in damage to equipment.
l
Water flow exceeding maximum flow rates will negatively affect the total pool filtration performance and may
damage the heat pump. This will not be covered under the equipment warranty.
MODEL
HEAT EXCHANGER
TYPE
FLOW RATES
MINIMUM
MAXIMUM
BB500 50 Hz 380 - 415
V
Titanium ThermoLink
®
120 GPM (454
L/min)
280 GPM (1060
L/min)
BB500 60 Hz 208 - 230
V
Titanium ThermoLink
®
120 GPM (454
L/min)
280 GPM (1060
L/min)
BB500 60 Hz 460 V
Titanium ThermoLink
®
120 GPM (454
L/min)
280 GPM (1060
L/min)
PLEASE NOTE -
If minimum flow rates are not met, heat pump performance is reduced and performance will
suffer. Internal safety devices may deactivate the heat pump with the following errors:
l
HIGH PRESSURE FAULT
l
HP5 SYSTEM LOCKOUT
l
LOW PRESSURE FAULT
l
LP5 SYSTEM LOCKOUT
l
Operate water filtration devices per manufacturer's specifications. Dirty filters can cause a reduction of water flow
to the heat pump. An increase of 7-10 psi (48 to 69 kPa) higher than the clean filter pressure typically reduces
flow rates. This requires the filter to be cleaned or back-washed.
l
Keep baskets free of debris. A large quantity of debris in the pump and skimmer baskets can reduce water flow.
l
Check for improper valve settings. A partially closed valve after the filter, or a full-open bypass around the heat
pump, will cause insufficient water flow through the heat pump.
l
The maximum static pressure (or operating pressure) is 50 psi (345 kPa). These specifications relate to the heat
pump only.
l
Code-specified whole system turnover rates must be satisfied.
1
-
Ins
ta
lla
tion
Содержание GBB
Страница 2: ......
Страница 25: ...Page 21 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Страница 29: ...Page 25 1 Installation...
Страница 32: ...Page 28 1 Installation...
Страница 36: ...Page 32 1 Installation...
Страница 37: ...Page 33 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Страница 41: ...Page 37 1 Installation...
Страница 43: ...Page 39 1 Installation...
Страница 46: ...Page 42 1 Installation...
Страница 50: ...Page 46 1 Installation...
Страница 53: ...Page 49 1 Installation...
Страница 55: ...Page 51 1 Installation...
Страница 74: ...Page 70 l Follow all National Electric Codes NEC and or State and Local guidelines 3 Appendix...
Страница 75: ...Page 71 3 8 Schematics Some schematics have been provided in the appendix of this manual 3 Appendix...
Страница 77: ......
Страница 78: ......