INSTALLATION AND USER MANUAL 

 

 

 

 

 

 

 

 

Содержание ECO550

Страница 1: ...Swimming Pool Heat Pump INSTALLATION AND USER MANUAL ...

Страница 2: ......

Страница 3: ...plication 4 II Features 4 III Technical Parameter 5 IV Dimension 6 V Installation instruction 7 VI Operation instruction 11 VII Testing 13 VIII Precautions 14 IX Maintenance 15 X Trouble shooting for common faults 16 ...

Страница 4: ...is switched off before opening the case NOTE A The swimming pool heat pump must be installed by a qualified electrician B To maximize your swimming comfort set proper heating temperature C Don t put obstacles near the air inlet and outlet of the heat pump D This heat pump has power off memory function E When the ambient temperature is below 0 degree make sure to switch off the main power and drain...

Страница 5: ...series of swimming pool heater has been optimized in factory refer to technical parameter table II Features 1 Sensitive and accurate temp control and water temp display 2 High pressure and low pressure protection 3 Exceeding low temp auto stop protection 4 Temp control compulsory defrosting 5 International brand compressor 6 High efficient titanium heat exchanger 7 Easy installation and operation ...

Страница 6: ...R410A 38 8oz Net weight 1834oz Water circulation flow 83 116L min Noise 50 dB A Notice 1 This product works well under water temp 50 95 air temp 32 109 efficiency will not be guaranteed out of this range Please take into consideration that the pool heater performance and parameters are different under various conditions 2 Related parameters are subject to adjustment periodically for technical impr...

Страница 7: ...picture above is the specification diagram of the pool heater for technician s installation and layout reference only The product is subject to adjustment periodically for improvement without further notice A B C D E F G H ECO550 314 589 312 340 960 290 74 658 机 C H D A E F G B ...

Страница 8: ...pes connection Note The swimming pool heater must be grounded Notice The drawing demonstration and layout of the pipes is only for reference 2 Electric Wiring Diagram Note 1 Must be hard wired no plug allowed 2 The swimming pool heater must be grounded ...

Страница 9: ...talled in a location with good ventilation 2 The frame must be fixed by bolts M10 to concrete foundation or brackets The concrete foundation must be solid and fastened the bracket must be strong and antirust treated 3 Don t stack substances that will block air flow near inlet or outlet area and no barrier within 20in behind the main heater or the efficiency of the heater will be reduced or even ha...

Страница 10: ...ould comply with the rated voltage of the products 2 Heater must be grounded 3 Wiring must be handled by a professional technician according to the circuit diagram 4 Set leakage protector according to the local code for wiring leakage operating current 30mA 5 The layout of power cable and signal cable should be orderly and not interfere with each other C Switch on after finishing all wiring constr...

Страница 11: ...ng illustration A minimum of 300mm of clearance from walls shrubbery equipment etc is required around the entire pump circumference This allows for ample air intake No less than 800mm clearance on the air outlet is required to prevent recirculation of air We recommend to not place the unit underneath eaves decks or porches as this causes recirculation of discharged air or the efficiency of the hea...

Страница 12: ...ct Silence mode ON OFF Note You may set the desired water temperature from 18 to 35 The on the right shows the inlet water temperature The on the left shows the outlet water temperature After you turn on the heat pump the fan will start to run in 3 minutes In another 30 seconds the compressor will start to run 2 2 1 Status on the display Auto Mode Defrost Mode Heating Mode ...

Страница 13: ...n and off Press the for 10 seconds to enter the timer setting The ON will be flashing to enter the Timer ON setting Press the and to adjust Timer ON time You can choose Timer on Display ON or Repeat Timer ON display 1 ON by pressing Then press to confirm When the ON stops flashing and OFF is flashing you enter the Timer OFF mode Press the and to adjust Timer OFF time You can choose Timer OFF Displ...

Страница 14: ...achine is on heating and the compressor is working continuously for 10 minutes press both and buttons for 5 seconds to start compulsory defrost Note the break between compulsory defrost needs to be more than 30 minutes The symbol of defrost is twinkling when machine is compulsory or auto defrost The period and ending of compulsory defrost is the same as auto defrost VII Testing 1 Inspection before...

Страница 15: ...r than the compressor D After the pool heat pump starts up check for any abnormal noise from the heater VIII Precautions 1 Attention A Set proper temperature in order to get comfortable water temperature to avoid overheating B Please don t stack substances that can block air flow near inlet or outlet area or the efficiency of the heater will be reduced or even stopped C Please don t put hands into...

Страница 16: ...s during running and later the power is restored the heater will start up automatically So please switch off the power supply when there is a power cut and reset temp when power is restored C Please switch off the main power supply in lightning and storm weather to prevent from machine damage that caused by lightning D If the machine is stopped for a long time please cut off the power supply and d...

Страница 17: ... Switch on the power Fuse burned Check to change the fuse The breaker is off Check to turn on the breaker Running but not heating Air inlet blocked Remove the obstacles Air outlet blocked Remove the obstacles 3minutes protection Wait patiently Set temp too low Set proper heating temperature If the above solution doesn t work please contact your dealer Don t try to repair the heater yourself Import...

Страница 18: ...tion 9 EA coil pipe heat exchanger overheat protection 10 Eb Ambient temperature too high or too low protection 11 Ed Anti freezing reminder not failure 12 P0 Controller communication failure 13 P1 Water inlet temp sensor failure 14 P2 Water outlet temp sensor failure 15 P3 Gas exhaust temp sensor failure 16 P4 coil pipe heat exchanger temp sensor failure 17 P5 Gas return temp sensor failure 18 P6...

Страница 19: ... running failure 27 F5 Compressor driver module over current protection 28 F6 Compressor driver module overheat protection 29 F7 Current protection 30 F8 Heat dissipation device overheat protection 31 F9 Fan motor failure 32 Fb Capacitor power filter plate No power protection ...