Installation Guide - GreaseShield

®

1850-PF 

• 

GS1850  Unit: 

Ensure that there is sufficient  clearance above and to the right of the unit for servicing 

purposes  (5.9"/150mm minimum). 

Inlet Pipe - 1½"/40mm: 

To be piped with a sufficient fall of no less than 1 in  40. 

Outlet Pipe  - 2"/54mm: 

To  be piped with a sufficient fall of no less than 1 in  40. 

4! 

Invert Inlet - 1¼"/32mm: 

Must be kept capped off with the 

1¼"/32mm 

FlexiPlumb  Endcap provided (for servicing use only) 

Decant Outlet Hose - ¾"/18mm: 

To be piped directly into the main  drainage pipe via  a vented  drainage  stack as shown. 

The  Hose must be fixed in place using the  drainage hose support provided. 

Pre-Filter: 

Ensure sufficient height above the Pre-Filter to  allow for removal and daily  maintenance of Pre-Filter basket. 

Pre-Filter Basket: 

A Pre-Filter basket must be installed into the pre-filter at all times. 

Pre-Filter Support Bar: 

The support bar must be installed  when attaching the Pre-Filter 

Vortex Flow Controller: 

Must be fitted to the Pre-Filter inlet connection. 

Sampling Point: 

Connected to the outlet of the unit:  it is essential in the analysis of effluent leaving the unit. 

Running Trap: 

The outlet of unit must be fitted with a running trap to reduce foul smells. 

FOG Container: 

Ensure that the container is not restricted or blocked for daily  maintenance. 

Hot Water Solenoid Valve: 

Hot water must be connected to the unit using the ¾" 

BSP (F/F} 

Red PVC  Hose provided,  water 

supply must not exceed 

3 bar 

pressure and 

60

°

C/140

°

F. 

In the case of high pressure a pressure reducing valve must  be 

used.  Mains water connections  must be  made via a WRAS approved isolation valve which follows a  WRAS  approved double 

check valve. 

Power Lead: 

The unit  must be plugged  into a 

13 amp 

rated 

IP56 

socket located below counter level. 

Interconnecting Pipework: 

All pipework must be clipped and properly supported. 

Stainless Steel Hygiene Stand  (Optional  Extra): 

GS1850 unit should  be installed  on a Stainless  Steel  Hygiene stand.  It can 

be adjusted  up to 

2"/50mm 

in height to allow the unit to be levelled on uneven surfaces and provide access for cleaning. 

vs 05/02

/

2020 