6RL SERIES OPERATION MANUAL
SECTION 4: TECHNICAL SPECIFICATIONS
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
6RL Series Regenerative DC Load Operation Manual
Page 28 of 204
4.2
5kW Models
–
380V~480Vac Input (-4)
5 kW
Model
6RL05-170-80-4 6RL05-70-200-4 6RL05-40-360-4 6RL05-30-500-4 6RL05-20-750-4
AC supply
Voltage
342...528 V
Phases
2ph, PE
Frequency
50/60 Hz ±10%
Efficiency
(2
≤ 92.5%
≤ 93.5%
≤ 93.5%
≤ 94.5%
≤ 94.5%
DC Input
Max. input voltage UMax
80 V
200 V
360 V
500 V
750 V
Max. input power PMax
5 kW
5 kW
5 kW
5 kW
5 kW
Max. input current IMax
170 A
70 A
40 A
30 A
20 A
Overvoltage protection range
0...1.1 * UMax
0...1.1 * UMax
0...1.1 * UMax
0...1.1 * UMax
0...1.1 * UMax
Overcurrent protection range
0...1.1 * IMax
0...1.1 * IMax
0...1.1 * IMax
0...1.1 * IMax
0...1.1 * IMax
Overpower protection range
0...1.1 * PMax
0...1.1 * PMax
0...1.1 * PMax
0...1.1 * PMax
0...1.1 * PMax
Max. allowed input voltage
1.2 * UNom
1.2 * UNom
1.2 * UNom
1.2 * UNom
1.2 * UNom
Min. input voltage for IMax
0.73 V
2.3 V
2.3 V
4.6 V
6.8 V
Input capacitance
ca. 770 μF
ca. 310 μF
ca. 310 μF
ca. 98 μF
ca. 60 μF
Temp.coef. for set values Δ/K
Voltage / current: 100 ppm
Voltage regulation
Adjustment range
0...81.6 V
0...204 V
0...367.2 V
0...510 V
0...765 V
Stability at ΔI
< 0.05% UMax
< 0.05% UMax
< 0.05% UMax
< 0.05% UMax
< 0.05% UMax
Accuracy
(1
(@23±5°C / 73±9°F)
< 0.1% UMax
< 0.1% UMax
< 0.1% UMax
< 0.1% UMax
< 0.1% UMax
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤ 0.2%
Remote sensing compensation
max. 5% UMax
Current regulation
Adjustment range
0...173.4 A
0...71.4 A
0...40.8 A
0...30.6 A
0...20.4 A
Stability at ΔU
< 0.15% IMax
< 0,15% INenn
< 0,15% INenn
< 0.15% IMax
< 0.15% IMax
Accuracy
(1
(@23±5°C / 73±9°F)
< 0.2% IMax
< 0.2% IMax
< 0.2% IMax
< 0.2% IMax
< 0.2% IMax
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤0.2%
Compensation 10-90% ΔUDC
< 0.6 ms
< 0.6 ms
< 0.6 ms
< 0.6 ms
< 0.6 ms
Power regulation
Adjustment range
0…5100 W
0…5100 W
0…5100 W
0…5100 W
0…5100 W
Stability at ΔI / ΔU
< 0.75% PMax
< 0.75% PMax
< 0.75% PMax
< 0.75% PMax
< 0.75% PMax
Accuracy
(1
(@23±5°C / 73±9°F)
< 1% PMax
< 1% PMax
< 1% PMax
< 1% PMax
< 1% PMax
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤ 0.2%
Resistance regulation
Adjustment range
0.02…25 Ω
0.1…150 Ω
0.3...520 Ω
0.5…1000 Ω
1.2…2200 Ω
Accuracy
(4
(@23±5°C / 73±9°F)
≤1% of max. resistance ± 0.3% of rated current
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
1.
Related to the nominal values, the accuracy defines the maximum deviation between an adjusted value and the true (actual) value on the DC
input. Example: a 170 A model has min. 0.4% current accuracy, that calculates as 680 mA. When adjusting the current to 80 A, the actual current
on the DC input is allowed to differ by a maximum of 680 mA, which means it may be between 79.32 A and 80.68 A.
2.
Typical value at 100% input voltage and 100% power
3.
The display accuracy adds to the accuracy of the related actual value on the DC input, so the display accuracy will be lower, i.e. the error will be
higher
4.
Includes the accuracy of the displayed actual value
Содержание 6RL Series
Страница 203: ......