background image

AIR FLOW

FILTER

FURNACE/AIR 

HANDLER

FRESH AIR 

INTAKE HOOD 

w/ SCREEN  

FRESH AIR INTAKE DUCT 

FRESH AI

R

GABLE END WALL, BAND JOIST, OR PORCH SOFFIT 

DEHUM 

VENTILATOR

RETURN 

MIXING BOX

10” DIA. DUCT

AIR FLOW

MODEL 6506 

NORMALLY CLOSED DAMPER

10x6 ROUND TRANSITION

+ - A B ODT VENT DEH

Sensor Dampers

Remote

FLOA

T

Switch

DH

DH

Gh
Rf

Cf

Gs

Y

W

HV

AC EQUI

P.

G

R

C

W

Y

R

C

G

W

Y

HVAC

EQUIPMENT THERMOSTAT

OPTIONAL

24 VAC

(10 VA min)

TRANSFORMER

6” NORMALLY

CLOSED DAMPER

OPTIONAL

EXTERNAL

VENTILATION

CONTROL

DUCTING AND WIRING

Install ducting as shown in 

Figure 7

 . 

A 6” diameter intake duct is usually 
sufficient, but a larger intake duct, or 
multiple 6” intake ducts can be used 
if added ventilation flow is needed .
A normally closed damper like the 
Aprilaire Model 6506 needs to be 
installed in the intake duct to comply 
with Energy Star Certified Homes 
requirements .

Wire the control to the HVAC system as show in 

Figure 8

 . 

Wiring to the HVAC system allows the ventilator to turn on 
when the HVAC system is running for improved circulation 
of the outdoor air, and to take advantage of the latent 
capacity of the air conditioning .
The ventilation output of a thermostat can wired to the 
DH terminals of the Model 8191 or 8192 to put control of 
ventilation in the living space . Aprilaire thermostat models 
with a ventilation output include: 8840M, 8840, 8920W, 
8830, 8910W, 8910, 8820, 8620W and 8620 . Note that 
an outdoor temperature sensor (included with all models) 
must be wired to the thermostat to take full advantage of 
all ventilation features .
Wiring to the Rf terminal of the ventilator is optional . 
Wiring as shown allows the fresh air brought in by the 
ventilator to be distributed to the entire home by the HVAC 
system fan when it would not be otherwise running .

FIGURE 7 – Ducting the Ventilator

FIGURE 8 – Wiring the Ventilator

90-1983

90-1985

DUCTING

WIRING

7

Содержание 8191

Страница 1: ...d in the upright position WARNING 1 120 Volts may cause serious injury from electric shock Disconnect electrical power before starting installation or servicing Leave power disconnected until installa...

Страница 2: ...ly designed homes while removing moisture from the air Simply duct the inlet of the ventilator to an outdoor air intake and duct the discharge to the return side of the HVAC system Plug the unit in se...

Страница 3: ...able TABLE 1A Model 8191 Ventilation Performance External Static w c Airflow CFM Power W Current A CFM watt CFM watt FAN ONLY 0 160 63 57 2 54 4 48 0 1 140 63 56 2 22 3 97 0 2 120 63 56 1 90 3 55 0 3...

Страница 4: ...ilator The outlet collar has a backflow damper The outlet duct collar may be attached to the top or end of the unit Move the outlet cover to the location not being used See Figure 2 Make sure there ar...

Страница 5: ...cure the control with the same four screws used to attach the control to the top of the unit 6 Secure the control panel cover to the top of the unit FIGURE 3 Control Location 90 1884 LOCATION CONSIDER...

Страница 6: ...ubing to curl up which may result in air lock NOTE Always use PVC primer and cement when connecting PVC drain line or the provided fitting to the dehumidifier drain outlet Always install the ventilato...

Страница 7: ...Certified Homes requirements Wire the control to the HVAC system as show in Figure 8 Wiring to the HVAC system allows the ventilator to turn on when the HVAC system is running for improved circulatio...

Страница 8: ...utes TABLE 3 Cycle Time Setting minutes for Airflow Delivered vs Airflow Required for 1 Hour Cycle CFM Delivered CFM Required 20 30 40 50 60 70 80 90 100 110 60 20 30 40 50 60 80 15 25 30 40 45 55 60...

Страница 9: ...854 An external control such as a thermostat can be used to turn ventilation on and off with External Control ENABLED The Remote Control option is not available when External Control is enabled Model...

Страница 10: ...or and all of the wired components will turn on and off during Installer Test Mode to demonstrate that all are properly operating Installer Test Mode lasts for four 4 minutes If the ON OFF button is p...

Страница 11: ...tween the DH terminals of the Model 8191 8192 control The external control determines when ventilation occurs Dehumidification of the incoming air is still controlled as described below even if an ext...

Страница 12: ...m water and a mild detergent solution 5 Shake off the excess water from the filter 6 Replace the filter making sure the filter is secured in both the top and bottom filter rails 7 Replace the filter a...

Страница 13: ...re is significantly lower than the air temperature the Frost Sensor will need to be replaced Part No 5455 5 If the sensor is OK turn up the humidity setting to seven 7 to turn on the compressor Allow...

Страница 14: ...ng Lack of or reduced airflow Check ventilator air filter and wash or replace Check for blocked duct work Inlet air conditions below 60 F Increase the humidity setting Inlet air temperature is outside...

Страница 15: ...5448 7 Outlet Duct Panel 5449 8 Backflow Damper 10 5450 9 Inlet Duct Panel 5451 10 Cover Outlet 5452 No Part Description Part No 11 Model 8191 Fan 5453 Model 8192 Fan 5467 12 Wire Harness Power 5454...

Страница 16: ...P O Box 1467 Madison WI 53701 1467 Phone 800 334 6011 Fax 608 257 4357 www aprilairepartners com 10010925 4 17 B2206395E Printed in U S A 2017 Aprilaire A division of Research Products Corporation...

Отзывы: