INSTALL DUCTWORK

DUCTING THE 8190FF
1. 

Install insulated ductwork from the 6" ventilation opening to the 
fresh air inlet hood.

2. 

Tape or mastic the duct to the hood and collar, and seal the duct 
insulation on the ends using zip ties or tape.

3. 

Install ductwork from the 10" 8190FF collar to a location with air 
representative of the whole house.  If the 10" duct is located in an 
unconditioned space such as an attic or garage, use insulated duct 
and tape/seal the duct and insulation as you would the fresh air 
intake duct.  Suggested dehumidifier inlet ducting:

•  Install a separate register with 10" collar in the space to be 

dehumidified.

•  Connect the 10" duct to a return air plenum or to the return 

air duct.

Refer to dehumidifier 

Installation Instructions

 and 

Owner’s Manual

 

for instructions for ducting the dehumidifier to your HVAC system.

WIRING THE 8190FF

Remove/turn off the fuse or circuit breaker that provides/will provide 
power to the dehumidifier before starting wiring.  Do not restore 
power until all wiring is complete.

1. 

Wiring to the Model E100V dehumidifier (see 

FIGURE 3

).

•  Use the included switched-power jumper wire and 2-wire 

connector to attach one of the 8190FF wires to one of the VENT 
terminals on the dehumidifier user interface.

•  Use the power harness included with the E100V dehumidifier 

to connect the dehumidifier power port to the unused VENT 
terminal and 8190FF wire.

2. 

Wire to a Model E100 or Model 1850 dehumidifier (see 

FIGURE 4

).

•  Use 18-22 AWG wire to attach one of the 8190FF wires to one of 

the VENT terminals on the dehumidifier user interface.

•  Install the 24VAC transformer, preferably to the junction box used 

for the dehumidifier power outlet.  Make sure the fuse or circuit 
breaker that serves the junction box to which the transformer is 
to be wired, has been removed/turned off

•  Use 2-wire cable, 22 AWG minimum, to connect the transformer 

to the unused VENT terminal and 8190FF wire.

Refer to dehumidifier 

Installation Instructions

 and 

Owner’s Manual

 

for instructions on wiring and ventilation setup.

+ - A B

ODT

VENT DEH

Sensor

Dampers

Remote

FLOA

T

Swit

ch

DH

DH

Gh
Rf
Cf
Gs

Y

W

HV

AC E

QUIP
.

G

R

C

W

Y

R

C

G

W

Y

HVAC

EQUIPMENT THERMOSTAT

OPTIONAL OUTDOOR TEMPERATURE 

SENSOR (MODEL 8052 INCLUDED)

E100V

EXTERNAL

24V PORT

ACTUATOR

+ - A B

ODT

VENT DEH

Sensor

Dampers

Remote

FLOA

T

Swit

ch

DH

DH

Gh
Rf
Cf
Gs

Y

W

HV

AC E

QUIP
.

G

R

C

W

Y

R

C

G

W

Y

24 VAC

(10 VA min)

TRANSFORMER

(NOT INCLUDED)

8190FF

ACTUATOR

OPTIONAL OUTDOOR TEMPERATURE 

SENSOR (MODEL 8052 INCLUDED)

HVAC

EQUIPMENT THERMOSTAT

90-2625

90-2626

FIGURE 3 

– WIRING INSTRUCTIONS FOR 8190FF TO E100V

FIGURE 4 

– WIRING INSTRUCTIONS FOR 8190FF TO OTHER

2