background image

TROUBLESHOOTING

Technical Support is available Monday through Friday, 7:00 a�m� to 5:00 p�m� CST, at (800) 334-6011� Use the guides on the following pages to identify 
and correct system faults� Contact Technical Support before replacing the unit or any components and for additional troubleshooting�

DIAGNOSTIC CODES

When an error occurs, the Diagnostic Code along with SERVICE REQUIRED 
will be displayed on the control screen�

TABLE 1 

– DIAGNOSTIC CODES

Diagnostic 

Code

Failure Mode

Action

Reset

E1

Internal Humidity or 

Temperature Sensor 

Open or Shorted

1. 

Check the connection between the sensor board and control board�

2. 

If connection okay, replace sensor board, Part No� 5460�

Cycle Power

E2

High Refrigeration 

Pressure

1. 

Verify that the fan works, and that there is nothing restricting air flow�

2. 

If the fault persists, call Technical Support�

Cycle Power

E3

Model 76 

Remote Control 

Communication Loss

1. 

Check connections between Model 76 and dehumidifier control board� Terminals should be fully 

inserted and secured in the control board and Model 76 control terminals�

2. 

If connections are correct and secure, turn off the dehumidifier and remove the Model 76� Use a short 

section of 4-wire cable to reconnect the Model 76 to the control board� Turn the dehumidifier back on 

and increase the dryness level setting on the Model 76� If the dehumidifier turns on, the problem is 

with the wiring between the dehumidifier and control�

3. 

If the dehumidifier does not turn on, call Technical Support�

Self-Correcting

E4

Insufficient Capacity

1. 

Check the frost sensor connection at the power board� Terminal should be fully seated on the power 

board pins�

2. 

Remove the side access panel and verify that the sensor is secured to the suction line�

3. 

If the sensor is connected and secured to the refrigeration line proceed to the next step� 

4. 

Reset the fault by cycling power to the dehumidifier�

5. 

Turn the humidity setting down (below room/home humidity level) to make a dehumidification call� 

6. 

Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic test 

mode by simultaneously pressing the 

 and MODE buttons for 3 seconds� The LCD will display 

the temperature measured by the internal sensor while also displaying AIR SAMPLING and ON, the 

humidity measured by the internal sensor while also displaying %RH and ON, and the frost sensor 

temperature while also displaying ON� Scroll through these values and by using the 

 and 

 

buttons� 

7. 

Record values and call Technical Support�

Cycle Power

E5

High Temperature 

Thermistor Failure

1. 

Check the high temperature sensor connection at the power board� Terminal should be fully seated 

on the power board pins�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the 

refrigeration line coming from the compressor�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5456 — contact Technical Support to confirm�

Cycle Power

E6

Low Temperature 

Thermistor Failure

1. 

Check the low temperature sensor connection at the power board�

2. 

Remove the side access panel and verify the sensor is not damaged and connected to the suction 

line�

3. 

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part 

No� 5455 — contact Technical Support to confirm�

Cycle Power

90-1854

9

Содержание 1872

Страница 1: ...tenance 3 Do not use in pool applications Pool chemicals can damage the dehumidifier 4 Do not use solvents or cleaners on or near the circuit board Chemicals can damage circuit board components 5 Wait 24 hours before running the unit if it was not shipped or stored in the upright position 6 Do not use dehumidification to prevent window condensation in the winter To address window condensation use ...

Страница 2: ...F 0 RH 99 RH non condensing Filter MERV 8 washable Airflow EXTERNAL STATIC PRESSURE w c AIRFLOW CFM 0 0 310 0 2 270 0 4 225 0 6 175 0 7 w c is maximum design external static pressure REMOVE SHIPPING BRACKET IMPORTANT Cut the strap securing the compressor shipping support bracket and remove the strap shipping bracket screws and bracket See FIGURE 1 CLIP OFF PLASTIC STRAP REMOVE SCREWS 2 DISCARD SHI...

Страница 3: ...the slip fit connection A level surface is required to ensure proper drainage from the dehumidifier Always install the dehumidifier in a condensate pan when locating in or above a finished space Adhere to local codes regarding draining of the condensate pan CONDENSATE PUMP AND FLOAT SWITCH If a condensate pump is needed install it in the condensate pan if installed Install a condensate overflow sa...

Страница 4: ... for an extended period when first installed Your dehumidifier is equipped with two features that protect against unwanted energy consumption Defrost is a normal operating mode that helps to prevent significant ice formation on the refrigeration system coil The dehumidifier display will show DEFROSTING when operating in this mode This mode can occur when there is not enough air moving through the ...

Страница 5: ...warm water and a mild detergent solution 5 Shake off the excess water from the filter 6 Replace the filter making sure the filter is secured in both the top and bottom filter rails 7 Replace the filter access door 8 Turn the ON OFF switch ON 9 Press the and buttons simultaneously for 3 seconds to clear the service message CHECK THE DRAIN The drain should be checked annually to ensure there are no ...

Страница 6: ... The on board control can be located on the top of the dehumidifier or can be relocated to the front of the dehumidifier if the control can not be seen accessed in the top orientation TO MOVE THE CONTROL 1 Remove the front control panel cover 2 Remove the filter access door and filter 3 Detach the on board control by removing the four 4 screws around the control Note Use one hand to support the bo...

Страница 7: ...ted to the supply side of the HVAC system Use a minimum of 12 of flex duct at the dehumidifier inlet and outlet to prevent vibration noise transmission When ducting return to return preferred the dehumidifier must be wired to turn on the HVAC fan when operating When ducting return to supply allow adequate space before the first branch duct to ensure the warm dehumidified air is thoroughly mixed wi...

Страница 8: ...is not ducted to the HVAC system REQUIRED COMPONENTS 10 Ductwork Grilles with 10 Duct Collars DEHUMIDIFIER DEHUMIDIFIED AIR IS SUPPLIED TO DUCTED SPACE AIR IS PULLED FROM DUCTED SPACE 10 MIN GRILLE WITH 10 DUCT COLLAR 2 PLACES DEHUMIDIFIED SPACE 90 2026 FIGURE 11 STAND ALONE DUCTED 8 ...

Страница 9: ...ower board Terminal should be fully seated on the power board pins 2 Remove the side access panel and verify that the sensor is secured to the suction line 3 If the sensor is connected and secured to the refrigeration line proceed to the next step 4 Reset the fault by cycling power to the dehumidifier 5 Turn the humidity setting down below room home humidity level to make a dehumidification call 6...

Страница 10: ...nstalled on the outlet side of the dehumidifier Check if backflow damper is blocked or stuck and remove obstruction Dehumidifier blower is running but compressor is not Float switch open If float switch installed check connections at control board and empty condensate pan If no float switch installed check that the jumper is installed at the float switch terminals on the control board Coil frostin...

Страница 11: ...Deh 5449 8 Backflow Damper 10 Deh 5450 9 Inlet Duct Panel AA Deh 5451 10 Cover Outlet AA Deh 5452 No Part Description Part No 11 Fan 130pt Deh with 10MFD Capacitor 5572 12 Wire Harness Power Deh 5454 13 Sensor Low Temperature Deh 5455 14 Sensor High Temperature Deh 5456 15 Capacitor 50MFD 370VAC 5594 16 Capacitor 10MFD 250VAC 5573 17 RH Sensor Deh 5460 18 Drain Tube Fitting 5665 19 Compressor Over...

Страница 12: ...ULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED WARRANTY IS VOID IF DEFECT S RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTA...

Отзывы: