Applied Comfort NFWC Series Скачать руководство пользователя страница 5

803809 Rev. 01  

All 277 Volt units are furnished with a NEMA 7-20P, 
20 Amp non-locking plug, and hence will require a 
NEMA 7-20R receptacle to be installed in the heating 
subbase. 
 

NOTE:

 These installations are not “cord connected” 

units; they are permanently connected per the National 
Electrical Code. The plug and cord are considered to be 
a “connector of convenience” in order to facilitate easy 
removal of the chassis for servicing. The plug and cord 
are suitably protected within the heating subbase. 
 
 

WARNING:

 To avoid property damage, bodily injury 

or death, the unit must be used on a grounded power 
supply only. The unit will be grounded through the 
service cord plug and matching receptacle as long as 
the branch circuit remains grounded. 

 
DO NOT: 

 

Change the length of the cord. 

 

Bend the connector blades or otherwise alter 
service cord plug configuration. 

 

Use extension cords. 

 

 

Wiring to Subbase 

 
Remove the junction box cover plate. Punch out 
the appropriate knock-out and anchor the electrical 
supply conduit to the junction box. Connect the 
power supply wires to the receptacle. Be sure to 
properly ground the electrical supply to the 
subbase and the receptacle using the two 

Green 

with Yellow Stripe 

ground leads provided. Mount 

the receptacle with the designated screws and re-
install the junction box cover plate.   

 
 
CHASSIS INSTALLATION 

 

Unpack heat/cool chassis from shipping carton.  
Check for any shipping damage. Spin the fan wheels 
manually to confirm free rotation. Inspect refrigerant 
piping to ensure there is no damage or potential 
chafing. Report any shipping damage to the carrier 
immediately. 

Check the interior of the installed wall sleeve. Clean 
out any dirt or debris that may have accumulated. 
Replace any air seals that are damaged or missing, if 
applicable.  

Heating/Cooling Chassis Installation 

 

1.

 

Locate the 

wall sleeve seal

 shipped with the unit and 

apply it to the top front flange of the wall sleeve, 
running even with the bottom edge of the flange (see 
illustration).  

 

 

2.

 

Slide the chassis into the wall sleeve until firmly 
seated against the seals. Push from the ends of the 
front cover where they attach to the coil supports. Be 
careful 

NOT

 to push the chassis from the electrical 

box cover or middle of the front coil cover.  

3.

 

The chassis must be level from side-to-side and 
sloped toward the outdoors from front-to-rear in the 
order of 1/8 inch per foot, once the chassis side 
flanges are drawn up tight to the wall sleeve using the 
four flange screws. A chassis slope downward 
(backward toward the room) from outdoor-to-indoor 
side is not permissible and must be corrected before 
the unit is operated. 

4.

 

There are vertical air seals at the rear of the unit that 
surround the condenser outlet that will engage and 
“seal” against the rear grille. However, in some cases, 
such as when an extra deep wall sleeve is used, or 
some other variation is encountered that prevents the 
air deflectors from sealing against the outdoor grille, 
then steps must be taken to add anti-recirculation 
baffles to prevent hot condenser air from short-
circuiting back into the air intake/outdoor blower inlet 
via the void space created in behind the outdoor grill. 

5.

 

Position the chassis in the wall sleeve cabinet and 
slide into place. Keep the chassis level, square, and 
centered to prevent binding. The chassis must be 
pushed into the wall sleeve until the side flange seals 
of the chassis engage the sleeve. Alternately tighten 
each of the four draw screws until the chassis is 
drawn snugly into the sleeve. Do not over-tighten the 
draw screws. 

Содержание NFWC Series

Страница 1: ...PACKAGED TERMINAL AIR CONDITIONER PTAC Cooling with Hot Water or Steam Heating INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Страница 2: ...or cooling during the building s construction stage To access the air filter first remove the grille cover from the heating subbase by rotating the two turn finger and thumb fasteners until the grille cover releases The unit front panel need not be removed The air filter is located directly below the heat exchange coil and slides out freely Always replace the grille cover after re inserting the fi...

Страница 3: ...sleeve has a 1 8 per foot slope downward toward the outside to ensure proper water drainage out the back edge of the sleeve during overflow conditions The specified slope corresponds to a 1 8 bubble on a carpenter s level The wall sleeve must also be level from side to side HEATING SUB BASE The heating subbase contains a tube and fin heat exchanger that is configured for the use with hot water or ...

Страница 4: ... tubes Always pipe the valve to the supply connection If the heating medium is hot water connect the valve outlet Supply to the lower connection and the Return water to the upper connection If the heating medium is steam connect the valve outlet Supply to the upper connection and the Return to the lower connection Route the steam or water source to the valve s inlet connection Install the piping v...

Страница 5: ...t or debris that may have accumulated Replace any air seals that are damaged or missing if applicable Heating Cooling Chassis Installation 1 Locate the wall sleeve seal shipped with the unit and apply it to the top front flange of the wall sleeve running even with the bottom edge of the flange see illustration 2 Slide the chassis into the wall sleeve until firmly seated against the seals Push from...

Страница 6: ...r in the bottom of the heating subbase so it is sure to sense true return air temperature and not air that has been heated by the heating coil Use the clamp provided to secure the bulb in place IMPORTANT To avoid damaging the indoor thermistor wire always remove the thermistor from the clamp holder before removing the chassis for service IMPORTANT Operating the unit without the filter in place can...

Страница 7: ...to operate the fan and set fan speeds Auto Mode will cycle the fan on and off and determine the fan speed in conjunction with the heating or cooling demand Warmer Key Pressing the Warmer Key will cause the display to show the set point temperature for 3 seconds and then increases room temperature by 1 degree for every subsequent press of the key Cooler Key Pressing the Cooler Key will cause the di...

Страница 8: ...ge personal injury or death Disconnect electric power to the unit before servicing A factory supplied 24 Volt wiring harness is provided with every unit to facilitate connection to the wall thermostat wiring One end has a multi pin connector which mates with a connector exiting the unit The other end has preinstalled butt splice connectors which play a dual role in insulating any unused connectors...

Страница 9: ... to be ON or OFF and whether the fan is to run continuously or to cycle with heating or cooling demand Figure 2 Once a comfortable temperature setting is established no other adjustments are necessary except for fan speed which may or may not be adjustable on your particular thermostat CAUTION One side of the unit s 24 volt control system is grounded When wiring the thermostat care must be taken n...

Страница 10: ... 22 The procedure to set the limits is as follows Depress the On Off key the F C key and the Warmer key simultaneously for 5 seconds to enter the limit setup mode The Warmer and Cooler keys will scroll through the R values indicated in the above table Once the desired R value has been obtained on the display press the On Off key to accept the change and then press it again to effect the change and...

Страница 11: ...from the Chassis Air Outlet by removing the screw located under the control door The Duct Plenum can now be installed Insert the Duct Plenum tabs into the slots provided in the Chassis Enclosure based on the direction you require the air discharge On the opposite end of the tabs there will be an existing screw location Use the screw removed previously to secure the Duct Plenum to the Chassis Air O...

Отзывы: