Room Freeze Protection 

This feature is enabled when the unit is shipped from 
the factory. The feature can be disabled by qualified 
service personnel. If power is available to the unit, and 
regardless of whether it is turned ON or OFF, the unit 
will automatically supply heat to the room with the fan 
running at low fan speed if the room temperature falls 
to 50°F (10ºC). The heat will turn off when the room 
temperature reaches 55°F (13ºC). For the feature to 
work, the unit must be configured with an electric 
heater. The feature is enabled whether the unit is 
configured for keypad or remote thermostat. The 
protection remains active when the unit is OFF, for 
either keypad or remote thermostat application, as long 
as the unit is plugged in, power is available, and a heat 
source is configured in the unit and is working.  
 

Compressor Short-Cycle Protection 

If the electronic control shuts the compressor down for 
any reason, a 3 minute time delay will elapse before the 
compressor is allowed to re-start. This prevents 
compressor overload during re-start due to unequal 
system refrigerant pressures. 
 

Indoor Coil Freeze Protection 

Control of frost on the evaporator coil due to low 
indoor loads, or cold outdoor ambient temperatures, is 
provided.  
 

Low Outdoor Temperature Lock-out 

If the outdoor temperature is too low for proper 
compressor operation, cooling operation will be 
suspended until the outdoor temperature rises to an 
acceptable point, depending on the application.     
 

Indoor Temperature Limiting (Keypad Control 
Only) 

Using the keypad control and display, high and low 
temperature limits can be established to prevent the 
user from entering set point temperatures colder or 
warmer than what the property manager or hotel 
operator may desire. The temperature limit choices are 
as follows: 
 
Configuration Code 

Low Limit °F 
(ºC) 

High Limit °F 
(ºC) 

R1 

63            (17) 

86            (30) 

R2 

65            (18) 

86            (30) 

R3 

65            (18) 

90            (32) 

R4 

67            (19) 

88            (31) 

R5 

67            (19) 

92            (33) 

R6 

69            (20) 

90            (32) 

R7 

69            (20) 

72            (22) 

 

The procedure to set the limits is as follows: 
Depress the On/Off key, the °F/°C key, and the 
Warmer key simultaneously for 5 seconds to enter the 
limit setup mode. The Warmer and Cooler keys will 
scroll through the R-values indicated in the above 
table. Once the desired R-value has been obtained on 
the display, press the On/Off key to accept the change, 
and then press it again to effect the change and restore 
the normal display. 

 
Automatic Powered Damper 

 
NFWC models are available with or without provision 
for fresh air. However, if the units are configured to 
bring in fresh air, they must have an automatic powered 
fresh air damper that opens the fresh air door to bring 
outdoor air into the room only when the indoor blower 
is running. If the indoor fan shuts off, the damper 
automatically closes and interrupts the heating coil’s 
potential exposure to possible extremely cold air when 
there is no blended air flow over the coil and/or no 
flow of the heating medium inside the coil. The factory 
default is fresh air with high speed fan operation only, 
but it can be changed to open with low speed fan 
operation only by having qualified service personnel 
re-wire the unit as shown on the specific wiring 
diagram affixed to the unit. 
 

WARNING: 

The speed conversion procedure involves 

exposure to high voltage electrical circuits in the 
control box in order to make the necessary change to 
the damper action tied to motor speed, and must be 
performed by qualified service personnel. Failure to do 
so could result in property damage, personal injury or 
death. Disconnect electric power to the unit before 
servicing. 

 
 
OPTIONAL AIR DUCT KIT: 

 
The NFWC series has been designed and certified 
for use with an optional external duct kit. It is 
recommended that only the Applied Comfort 
Products duct kit be installed on the unit. 
 
The NFWC has been designed to use a 4.5” tall by 
7.5” wide insulated (3/8” insulation) Duct Plenum 
fastened to the top of the unit, which connects to a 
maximum 48” long insulated (1/4” insulation) 
Extension Duct of the same size, and uses an Air 
Terminal Grille at the end of the Extension Duct 
having an actual outlet area of 

7.25”x 4.25” with 

Содержание NFWC Series

Страница 1: ...PACKAGED TERMINAL AIR CONDITIONER PTAC Cooling with Hot Water or Steam Heating INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Страница 2: ...or cooling during the building s construction stage To access the air filter first remove the grille cover from the heating subbase by rotating the two turn finger and thumb fasteners until the grille cover releases The unit front panel need not be removed The air filter is located directly below the heat exchange coil and slides out freely Always replace the grille cover after re inserting the fi...

Страница 3: ...sleeve has a 1 8 per foot slope downward toward the outside to ensure proper water drainage out the back edge of the sleeve during overflow conditions The specified slope corresponds to a 1 8 bubble on a carpenter s level The wall sleeve must also be level from side to side HEATING SUB BASE The heating subbase contains a tube and fin heat exchanger that is configured for the use with hot water or ...

Страница 4: ... tubes Always pipe the valve to the supply connection If the heating medium is hot water connect the valve outlet Supply to the lower connection and the Return water to the upper connection If the heating medium is steam connect the valve outlet Supply to the upper connection and the Return to the lower connection Route the steam or water source to the valve s inlet connection Install the piping v...

Страница 5: ...t or debris that may have accumulated Replace any air seals that are damaged or missing if applicable Heating Cooling Chassis Installation 1 Locate the wall sleeve seal shipped with the unit and apply it to the top front flange of the wall sleeve running even with the bottom edge of the flange see illustration 2 Slide the chassis into the wall sleeve until firmly seated against the seals Push from...

Страница 6: ...r in the bottom of the heating subbase so it is sure to sense true return air temperature and not air that has been heated by the heating coil Use the clamp provided to secure the bulb in place IMPORTANT To avoid damaging the indoor thermistor wire always remove the thermistor from the clamp holder before removing the chassis for service IMPORTANT Operating the unit without the filter in place can...

Страница 7: ...to operate the fan and set fan speeds Auto Mode will cycle the fan on and off and determine the fan speed in conjunction with the heating or cooling demand Warmer Key Pressing the Warmer Key will cause the display to show the set point temperature for 3 seconds and then increases room temperature by 1 degree for every subsequent press of the key Cooler Key Pressing the Cooler Key will cause the di...

Страница 8: ...ge personal injury or death Disconnect electric power to the unit before servicing A factory supplied 24 Volt wiring harness is provided with every unit to facilitate connection to the wall thermostat wiring One end has a multi pin connector which mates with a connector exiting the unit The other end has preinstalled butt splice connectors which play a dual role in insulating any unused connectors...

Страница 9: ... to be ON or OFF and whether the fan is to run continuously or to cycle with heating or cooling demand Figure 2 Once a comfortable temperature setting is established no other adjustments are necessary except for fan speed which may or may not be adjustable on your particular thermostat CAUTION One side of the unit s 24 volt control system is grounded When wiring the thermostat care must be taken n...

Страница 10: ... 22 The procedure to set the limits is as follows Depress the On Off key the F C key and the Warmer key simultaneously for 5 seconds to enter the limit setup mode The Warmer and Cooler keys will scroll through the R values indicated in the above table Once the desired R value has been obtained on the display press the On Off key to accept the change and then press it again to effect the change and...

Страница 11: ...from the Chassis Air Outlet by removing the screw located under the control door The Duct Plenum can now be installed Insert the Duct Plenum tabs into the slots provided in the Chassis Enclosure based on the direction you require the air discharge On the opposite end of the tabs there will be an existing screw location Use the screw removed previously to secure the Duct Plenum to the Chassis Air O...

Отзывы: