background image

FIRE DETECTORS LIMITED

XP95 Manual Call Point (EN54)

Installation Guide

General

The XP95 Manual Call Point (EN54) is available in two versions:

–   part no. 55100-905, non-isolated red Manual Call Point with a standard backbox 

for surface wiring. 

–   part no. 55100-908, isolated red Manual Call Point with a standard backbox for 

surface wiring.

Installation

1.  Fit the backbox (

Fig 1

) to the wall.

2.  Run the cables from the loop into the backbox and connect them to the terminal 

blocks as shown in 

Fig 2

.  Ensure that functional earth/screen continuity is maintained. 

Screens should be connected to the yellow terminal block marked 1–4 on the black 

PCB cover.

3.  If a loop continuity test is to be done, it should be carried out before securing the call 

point to the backbox (step 5). Insert the continuity links supplied with the backbox (

Fig 

3

) into the terminal blocks before testing. After testing for continuity remove the con-

nectors and store for re-use.

4.  Set the unit address on the DIL switch in accordance with the address table overleaf.

5.  Unlock the small front cover by inserting the forked key and pushing it home. Pull the 

cover down and towards you and remove the deformable element. Connect the 

terminal blocks as shown in 

Fig. 2

, secure the call point to the backbox and re

fi

 t the 

deformable element as required. Finally, replace the front cover in the reverse order in 

which it was removed and push it up until it locks.

Troubleshooting

Before investigating individual units for faults, it is important to check that the system wiring 

is fault free.  Earth faults on data loops or interface zone wiring may cause communication 

errors.

Many fault conditions are the result of simple wiring errors.  Check all connections to the 

unit. Do not overtighten screws when mounting the backbox as this will cause distortion of 

the moulding.

Fault Finding

 Problem 

Possible 

Cause

  No response or missing 

Incorrect address setting

 

 

Incorrect loop wiring

 Alarm 

condition 

 

Glass or element incorrectly 

fi

 tted or broken

 

 

Test key not removed

Routine testing

Insert the test key into the hole at the bottom of the call point and push home. Observe 

routine test requirements as speci

fi

 ed in EN54–11: 2001 or the applicable local code.

Resetting

After testing reset the call point by removing the test key and pushing up the front cover 

until it clicks home.

Transparent hinged cover

To provide additional protection against accidental operation, a transparent hinged cover 

with a locking tag, part no 26729-152 is available, which can be 

fi

 tted to the manual call 

point included with this guide.

Please note that the call point does not conform to EN54–11 : 2001 when this lid is fi tted and 

secured with the locking tag supplied.

For further information, please refer to the XP95 Engineering Product Guide, PP1039. For 

isolator operation information refer to PP2090. Both documents are available on request.

© Apollo Fire Detectors Limited 2006

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hampshire, PO9 1JR, UK

Tel: +44 (0) 23 9249 2412   Fax: +44 (0) 23 9249 2754

 Email: techsales@apollo-

fi

 re.co.uk   Website: www.apollo-

fi

 re.co.uk

1

Part No 39214-267/Issue 2

Отзывы: