background image

©Apollo Fire Detectors Limited 2011

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK

Tel +44 (0)23 9249 2412  Fax +44 (0)23 9249 2754 

Email: techsales@apollo-fi re.co.uk Website: www.apollo-fi re.co.uk

4

1

Sounder Control Unit

Installation Guide

General

The Sounder Control Unit, part no 55000-852, is designed to control a zone of sounders 

powered by an external DC supply. It is supplied with a backbox for surface mounting and has 

an integral isolator as standard. 

Note: The Sounder Control Unit is not designed for outdoor use unless it is mounted in a suitable 

weatherproof enclosure.

Installation

1.  Mount the backbox as required and install all cables for termination. Ensure that earth 

continuity is maintained.

2.  Remove the cover plate (if secured) from the Sounder Control Unit assembly by inserting 

the blade of a terminal screwdriver into each of the four securing clips in turn, gently 

prising the outer edge of the cover plate over the clips underneath. DO NOT USE EXCESSIVE 

FORCE.

3.  Terminate all cables observing polarity.

 

Note: Cable length to be kept 3m or under.

4.  Gently push the completed assembly towards the backbox until the mounting holes are 

aligned and secure with the two mounting screws provided. DO NOT OVERTIGHTEN.

5.  Set the address of the unit as shown on page 3.

6.  Finally, when commissioning is complete, fi t the cover plate by placing it in position, 

observing the correct orientation (LEDs on the PCB must be aligned with viewing holes). 

Apply pressure to the cover plate until all four clips are holding it in position.

39214-129/2011/Issue 3

The cause and effect programming (the control panel software responsible for switching 

sounders and outputs etc. in alarm condition) should be fully checked, along with all 

equipment connected to the Sounder Control Unit.

Note: If this product has been subjected to excessive shock during transportation, it may be 

received with the relay contacts in the ‘set’ position. Reset the relay by subjecting it to one 

operating cycle before commissioning the system.

Functional Test Data

 

output bit  function 

input bit  function

 

2   group mode*  

2  group mode

 

  1 = off 

  1 = group

 

  0 = on 

  0 = individual

 

1  pulsed mode 

1  pulsed mode confi rmed

 

  1 = on   

  1 = on

 

  0 = off 

  0 = off

 

0  continuous mode  

0  continuous mode confi rmed

 

  1 = on   

  1 = on 

 

  0 = off 

  0 = off

*Note: group mode is disabled if the group address DIL switch is set to ‘0000’, irrespective of the 

protocol message

Troubleshooting

Before investigating individual units for faults, it is very important to check that the system wiring 

is fault free. Earth faults on a data loop or any ancillary zone wiring may cause communication 

errors. Many fault conditions are the result of simple wiring errors. Check all connections to the 

unit and make sure the correct value resistors are fi tted where necessary. 

Fault Finding

 

Problem Possible 

Cause

 

No response or missing 

Incorrect individual address setting 

 

 

Incorrect loop wiring

 

Fault condition reported 

Incorrect group or individual address setting

 

 

Incorrect wiring of sounder zone or fault input

  

Faulty 

sounder

 

 

Local supply faulty or polarity incorrect

 

 

Fuse blown on sounder PCB

 

Sounders do not operate 

Incorrect wiring

 

 

Incorrect group address setting

 

 

Fuse blown on sounder PCB

 

 

Incorrect cause and effect programming

  

Faulty 

sounder

  

Panel 

fault 

 

Sounders operate continuously 

Incorrect sounder zone wiring

 

Analogue value unstable 

Dual address

 

 

Loop data fault, data corruption

Отзывы: