background image

XP95 Sounder VAD Bases 

 Installation Guide

General

This guide describes the installation of the following base variants

Part number

Product Description

Category

45681-705

XP95 Sounder VAD Base (White) with Isolator

O

45681-709

XP95 VAD Base (White) with Isolator

O

45681-292

White Cap only (Lockable)

N/A

45681-293

Red Cap only (Lockable)

N/A

Connect the devices only to control panels using the XP95 protocol.

The XP95 Sounder VAD Bases combine a sounder with a visual alarm and a detector base in one unit. 

The VAD is activated whenever the sounder is active and cannot be controlled separately.

All XP95 Sounder VAD Base variants with short circuit isolator have a yellow LED which illuminates through 

the moulding if a short circuit is detected on the loop wiring (see Fig 1). 

Note: All 

XP95 Sounder VAD Base 

variants are not suitable for outdoor use.

Mounting Instructions

All base variants may be secured to a UK standard conduit box or surface mounted (providing there is 

access through the surface for cabling). If a detector is   tted, lock it if required by screwing in the grub 

screw in the detector with a 1.5mm hex driver (part no 29600-095).

The XP95 Sounder VAD Bases are ceiling mounted devices.  For coverage volume information please refer 

to PP2478.

Wiring Details

Note: These products are polarity sensitive (supply reversal protected) and will not function if wired 

incorrectly.

Terminate all loop cables in the two way terminal blocks. Connect the incoming loop cables to L1 IN (–) 

and L2 (+) and the outgoing cables to L1 OUT (–) and L2 (+). Functional earth or screen may be connected 

to the EARTH connection. The isolator LED can be seen through the moulding as shown in Fig 1.

DO NOT CONNECT LOOP CABLES TO THE OUTER TERMINALS OF ISOLATED MODELS.

When using as a stand-alone unit, a cap is available (red cap part no 45681-293 or white cap part no 45681-

292) and is secured with a 1.5mm, AF hexagon socket head screw. A hexagonal driver (part no 29600-095) 

is available from Apollo.

Technical Data

              

Operating Voltage 

 

 

 

              17—28V DC

Sounder Output

  High Tone Setting Volume 

 nominally 75dB(A) to 91dB(A)

  (Complies to EN54-3)

  Low Tone Setting Volume* 

nominally 55dB(A) to 75dB(A)

Sound pressure level information published in document PP2203 and isolator operation information 

published in document PP2090, both available on request.

 

Current Consumption at 24V DC

 

Quiescent 

350µA

 

Switch on Surge 

1.2mA for 1 sec

 

Sounder/VAD Operating 

14mA

 

VAD Frequency 

0.5Hz

 

IP Rating 

IP21C

*Low tone setting does not comply to EN54–3 and should not be used for   re  alarm applications

© Copyright Apollo Fire Detectors Limited 2013

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hants, PO9 1JR, UK

Tel +44 (0)23 9249 2412  Fax +44 (0)23 9249 2754

Email: techsales@apollo-  re.co.uk Website: www.apollo-  re.co.uk

XPERT Card Addressing

Select the desired address and remove the pips indicated in black. Remove pips with a small screwdriver.

Part Number

Primary Tone

Secondary Tone

45681-705

Apollo Evacuation Tone 

567Hz for 0.5s, 850Hz for 0.5s

Apollo Alert Tone

1s off, 1s 850Hz

Tone Table

39214-788/Issue 4

1

5

www.acornfiresecurity.com

www.acornfiresecurity.com

Отзывы:

Похожие инструкции для 45681-705