API IsoSplitter APD 41390 Скачать руководство пользователя страница 1

Thermocouple Input to Dual Thermocouple Output Splitter/Converter, Factory Ranged 

APD 41390

1 Input:

 

Any Thermocouple

2 Outputs:

  Any 2 Thermocouples, Alarm Relay Options

 

O

Split or Convert a T/C to Any Two T/C Types

 

O

Add Additional Isolated Output to Existing T/C

 

O

Zero and Span Output Calibration

 

O

Input LoopTracker

®

 

Q

Split/Convert Thermocouples for PLC Input, Control 
or Validation

 

Q

Interface Thermocouples with Panel Meters, PLCs, 
Recorders, Data Acq., DCS, & SCADA Systems

Applications

Description

The APD 41390 accepts a thermocouple temperature input and 
provides two independent thermocouple outputs. This makes 
it useful to match up the available thermocouple type with 
an instrument T/C input, for data recording, or when isolating 
inputs and outputs.
The thermocouple types are factory set. Both output tempera-
tures correspond to the input temperature and are limited by 
the smallest ANSI temperature range of the three T/C types you 
select. Each T/C type may be different if desired. Use appropri-
ate thermocouple extension wire as needed.
The input is sampled, CJC compensated, digitally converted to 
a linearized temperature signal, and then passed to the output 
stages where it is converted to two simulated thermocouple 
outputs with CJC compensation. Contact factory if the CJC 
compensation is to be disabled.

Full 4-way galvanic isolation (input, output 1, output 2, power) 
make this module useful for ground loop elimination, common 
mode signal rejection, and noise pickup reduction. 

LoopTracker 

An API exclusive feature includes a green LoopTracker LED that 
varies in intensity with changes in the process input signal. 
It provides a quick visual picture of your process input at all 
times and can greatly aid in saving time during initial startup 
and troubleshooting. 

Thermocouple Input, Factory Set

T/C types: 

J, K, T, E, M, N, P, R, S, B, C, D, G

Temp. range: Full ANSI range, or specify °F or °C range 
Linearity: 

±0.1°C and 0.001°C resolution  

Linearization: Polynomials, 1°C segments for types M and P 
T/C CJC:  

Automatic 

T/C current:  Less than 10 µA, including burnout sense 
T/C burnout:  Upscale (standard), 

B

: downscale, 

N

: none 

Custom: 

Provide T/C millivolt data, °F or °C range

Status LEDs

LoopTracker: 

Variable brightness green for input level 

Yellow LED: 

Error status 

Red/green LED:  Alarm state (with alarm option only)

Thermocouple Output, Channel 1, Factory Set

T/C types: 

J, K, T, E, M, N, P, R, S, B, C, D, G

Temp. range: Limited by smallest ANSI T/C range 
Linearity: 

To temperature 

Linearization: Polynomials, 1°C segments for types M and P 
T/C CJC:  

Automatic, can be factory disabled

Thermocouple Output, Channel 2, Factory Set

T/C types: 

J, K, T, E, M, N, P, R, S, B, C, D, G

Temp. range: Limited by smallest ANSI T/C range 
Linearity: 

To temperature 

Linearization: Polynomials, 1°C segments for types M and P 
T/C CJC:  

Automatic, can be factory disabled

Output Calibration

Zero and span potentiometers for each output, ±15% range

Output Resolution

16 bit

Output Ripple and Noise

Less than ±0.2% of span

Optional Alarm Relay

Single setpoint dual DPST contact sets, factory configured 
1 Form A (NO) and 1 Form B (NC) contact sets (4 terminals) 
May be field wired for Form C operation
8 A max @ 240 VAC 
resistive load 
Use external contact 
protection (RC snub-
ber) for inductive loads
Red/Green bi-color 
LED for alarm status
One set point, 12 
turn potentiometer, 
0-100% of span 
One reset point, 12 
turn potentiometer, 0-100% of span 
Default: HI alarm, non-latching, normal acting (failsafe)
Relay Test button toggles relay to opposite state or resets 
relay with HT option

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 
Better than ±0.02% of span per °C stability

Response Time

500 milliseconds minimum

Isolation

Full 4-way galvanic: input, output 1, output 2, power 
1200 V

RMS

 min. 

600 VACp or 600 VDC common mode protection 
75 dB minimum common mode rejection 
Simultaneous 50 Hz and 60 Hz rejection

Housing and Connectors

IP 40, requires vertical installation on a 35 mm DIN rail inside 
a panel or enclosure. Allow room for air flow. 
For use in Pollution Degree 2 Environment 
Eight 4-terminal removable connectors, 14 AWG max. wire size

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 6 W maximum 
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 6 W maximum

Dimensions

1.78" W x 4.62" H x 4.81" D  
(45 mm W x 117 mm H x 122 mm D)

© 02-20

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

A

BSOLUTE

BSOLUTE

 P

 P

ROCESS

ROCESS

 I

 I

NSTRUMENTS

NSTRUMENTS

Free Factory 

I/O Setup!

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

  H H H H H

 H H H H H H

Made in USA

Applications Link 

api-usa.com/apps

Pb

Lead 

Free

How to Order

Factory Ranged and Configured

Options

Model

Power

Input

Outputs

Alarm

Code

Description

APD 41390

85-265 VAC, 60-300 VDC

Specify 

T/C type,  

temperature 

range in  
°F or °C

Ch. 1  

specify  

T/C type

Ch. 2  

specify 

T/C type

none

-

B
N

RA

HP
HT

U

Upscale burnout (standard)
Downscale burnout
No burnout, last valid value

Reverse-acting alarm

Latching relay, power-off reset
Latching relay, push button reset

Conformal coating for moisture 
resistance

APD 41390 D

9-30 VDC, 10-32 VAC

APD 41390 H

85-265 VAC, 60-300 VDC

HI alarm 

(failsafe std.)

APD 41390 DH

9-30 VDC, 10-32 VAC

APD 41390 L

85-265 VAC, 60-300 VDC

LO alarm 

(failsafe std.)

APD 41390 DL

9-30 VDC, 10-32 VAC

Optional Alarm 

Relay

Input 

LoopTracker 

LED

Zero and 

Span for 

Each Output

Removable Plugs

1     2     3     4

5     6     7    8

9   10   11   12

13   14   15   16

25   26   27   28

29   30   31   32

17   18   19   20

21   22   23   24

See Wiring 

Diagrams on 

Next Page

Universal 

Power

Quick Link: 

api-usa.com/tc

Status LED

Note: Temperature range is limited by the smallest ANSI 
range of the three T/C types selected.

Switching Current (A)

Switching Voltage (V)

3  5  10 

30 50 100  300 500

8

5

3

1

0.5
0.3

0.1

AC inductive load 

(cos 

f

 = 0.4)

AC resistive 

load

DC inductive load 

(L/R = 7 ms)

DC resistive 

load