Frequency Input Alarm Trips, Factory Ranged Input
APD 1700, APD 1720
Input:
0-25 Hz to 0-20 kHz
Output:
Two 8 Amp SPDT Relays
O
Factory Set Frequency Input Range
O
Adjustable Setpoint and Deadband Potentiometers
O
Input LoopTracker
®
and Alarm Status LEDs
O
Full 1200 V Isolation
O
Alarm Test, Optional Reset Button
Q
Machinery Speed Alarm
Q
Redundant or Backup Alarm
Q
Conveyor or Machine Malfunction Alarm
Frequency Input Range
Factory configured, please specify input type and range
Frequency:
0-25 Hz to 0-20 kHz
Sine wave, sawtooth, or square wave with min. 5 µsec pulse
Input Impedance
At maximum sensitivity: 10 k
W
nominal
At minimum sensitivity:
100 k
W
nominal
Input Sensitivity/Hysteresis
Multi-turn potentiometer for sensitivity adjustment
Maximum sensitivity:
±25 mV typical
Minimum sensitivity:
±2.5 V typical
Input Amplitude Range
100 mV to 150 V
RMS
Any waveform with minimum 100 mV amplitude change
Input Power Supply
15 VDC ±10%, regulated, 25 mADC, max. ripple, <10 mV
RMS
May be used to power sensor
Input Protection
Normal mode:
200% of input rating
Common mode:
600 VDC or 600 VACp input to ground
LoopTracker
Variable brightness LED indicates input loop level and status
APD 1700 Relay Output
Dual SPDT Form C contact sets operating in unison
1 setpoint adjustment, 1 deadband adjustment
Standard: HI alarm, non-latching, normal acting
Options: LO alarm, latching, reverse acting
APD 1720 Relay Output
2 independent SPDT Form C contact sets
2 setpoint adjustments, 2 deadband adjustments
Factory configured alarm
Standard: HI/LO alarm, non-latching, normal acting
Options: LO/LO, HI/HI, LO/HI alarms, band alarms,
latching, reverse acting
Relay Contact Ratings
8 A max @ 240 VAC resistive load
External contact protection such as an RC snubber is recom-
mended for inductive loads
Setpoint
12 turn potentiometer adjustable from 0 to 100% of span
Deadband
12 turn potentiometer adjustable from 1 to 100% of span
Output Test/Reset Button
Front button or external contact closure toggles relays to
opposite state when pressed.
Resets relay if latching relay option is ordered.
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than 0.04% of span per °C
Switching Current (A)
Switching Voltage (V)
0
3 5 10
30 50 100 300 500
8
5
3
1
0.5
0.3
0.1
AC inductive load
(cos
f
= 0.4)
AC resistive
load
DC inductive load
(L/R = 7 ms)
DC resistive
load
Alarm Options
—
add to end of model number
L
APD 1700 with LO trip. Alarm trips on decreasing signal.
HH
APD 1720 with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL
APD 1720 with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
LH
APD 1720 with LO/HI trip. Alarm 1 trips on decreasing
signal. Alarm 2 trips on increasing signal.
BA
APD 1720 with band alarm. Alarm trips if signal is
outside LO and HI trip points.
IBA
APD 1720 with inverse band alarm. Alarms trip if signal
is between LO and HI trip points.
HT
Latching alarm with push button reset
HP
Latching alarm with power-off reset. Module power
must be turned off to reset alarms
RA
Reverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4
Spare removable 4 terminal plug, black
Applications
Dimensions
0.89" W x 4.62" H x 4.81" D
(22.5 x 117 x 122 mm)
Height includes connectors
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Description
The APD 1700 and APD 1720 accept a frequency input and
provides a visual alarm indication and alarm relay contact
outputs.
The input is factory configured to a specific frequency
input range. The input can be of any type as long as it has
a minimum of 100 mV amplitude change and a minimum 5
microsecond pulse width. Input sensitivity is potentiometer
adjustable.
Front-accessible potentiometers are used to adjust alarm
setpoint and deadband.
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies
in intensity with changes in the process input signal.
A red/green bicolor alarm status LED (two on the APD 1720)
visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.
Output Test / Unlatch
The API exclusive Output Test button can be used to verify the
alarm and system operation and also provides the additional
function of unlatching the alarm when the latching option has
been ordered. This feature can be remotely operated.
The output test button greatly aids in saving time during initial
startup and/or troubleshooting.
©
03-22
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
Model
Input
Standard Alarm Configuration
Power
APD 1700
Factory ranged
specify frequency range
0-25 Hz to 0-20 kHz
Single setpoint dual SPDT relays
HI alarm, non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1700 D
9-30 VDC or 10-32 VAC
APD 1720
2 setpoints, 2 SPDT relays
HI/LO alarms, non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1720 D
9-30 VDC or 10-32 VAC
Universal Power
Alarm Status LED
Input LoopTracker LED
Alarm Test Function
Adjustable Deadband
Two 8 Amp SPDT
Alarm Relays
Custom Input Ranges
Removable Plugs
File E145968
85-265 VAC, 60-300 VDC
model only
Adjustable Setpoint
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
See Wiring
Diagrams on
Next Page
1 2 3 4
5 6
7 8
9 10 11 12
13 14 15 16
Applications Link