A54-3144-XR • Rev B
23
APCON, Inc.
ACI-3144-XR Chassis User Manual
Chapter 3. Specifications and compatibility
• Connect the chassis directly to the DC supply system earthing electrode conductor.
The chassis may also be connected to a bonding jumper from an earthing terminal bar
or bus to which the DC supply system earthed electrode conductor is connected.
• Locate the DC supply source within the same premises as the chassis.
• Any switching or disconnecting devices shall not be placed in the earthed circuit
conductor between the DC source and the point of connection on the earthed
electrode conductor.
Ensure that the socket outlet from which the equipment is powered provides a connection
to the building protective earth. If not, the service person planning for installation must
arrange for the installation of a protective earthing conductor from the separate earthing
terminal on the chassis to the protective earth wire in the building.
Specifications for interfaces
The following are the specifications for the
system controller
interfaces on an
I
NTELLA
F
LEX
XR chassis.
LAN ports
The LAN ports on the Controller panel manage the network connection from an
I
NTELLA
F
LEX
XR chassis to your network. Specifications for the
LAN ports 1 and 2
on the
Controller panel are as follows.
Serial port
The serial port is used for remote software management. Connect the RJ-45 module cable
from the RS-232 serial port on the back panel of the chassis to the COM port on a host
laptop or desktop, then use CLI commands to configure the unit.
The specifications for the serial port are as follows:
Use the RJ-45 modular cable and the RJ-45 to DB-9 adapter to connect the chassis from
the serial port directly to a laptop or other host computer. This connection lets you
communicate directly with the chassis using CLI commands. For connection instructions,
see
Use CLI to configure the chassis
The following tables list the pin signals for each connector.
Item
Description
Protocol/Interface
100/1000BASE-T Ethernet, TCP/IP
Both enabled
Maximum cable length
100 meters/300 ft
Rear panel connectors (2)
RJ-45
Specification
Description
Baud rate
115.2 KBaud
Mode
No parity, 8 bits, 1 stop bit
No software flow control
Maximum cable length
15 meters/50 ft
Rear panel connector
RJ-45
Содержание ACI-3144-XR
Страница 6: ...APCON Inc 6 A54 3144 XR Rev B Contents ACI 3144 XR Chassis User Manual...
Страница 16: ...APCON Inc 16 A54 3144 XR Rev B Chapter 2 Introducing the chassis ACI 3144 XR Chassis User Manual...
Страница 30: ...APCON Inc 30 A54 3144 XR Rev B Chapter 3 Specifications and compatibility ACI 3144 XR Chassis User Manual...
Страница 84: ...APCON Inc 84 A54 3144 XR Rev B Chapter 6 Maintain the chassis ACI 3144 XR Chassis User Manual...
Страница 90: ...APCON Inc 90 A54 3144 XR Rev B Index ACI 3144 XR Chassis User Manual...