• Case #1: If more water was consumed in the last 24 hours than in the 24 hours that precede, the
controller will determine how much more water was consumed and will convert this value in percent.
If the surplus (in %) is higher than the “High Alarm” limit, the controller will set off an alarm.
• Case #2: If less water was consumed in the last 24 hours than in the 24 hours that precede, the con-
troller will determine how much less water was consumed and will convert this value in percent. If
the deficit (in %) is higher than the “Low Alarm” limit, the controller will set off an alarm.
Before it can start monitoring the water consumption alarms, the controller needs to gather consumption
data for 48 hours in a row (no consumption alarm can be detected within this 48 hour delay). On initial
controller startup: the 48 hour countdown starts when the water meter is enabled. At the beginning of a
group: the 48 hour countdown starts at the startup of a new group. After a water consumption alarm, the
48 hour countdown starts after having acknowledged a high or low consumption alarm.
Setting the Alarm Start and Stop Temperatures
1. Using the menu select arrow keys, navigate to
Start / Stop Temps→Alarms
.
2. Set the following parameters:
Clean mode
Set the temperature below which a temperature alarm sets off during the clean
mode.
Low/High Alarm
Set the room temperature below and above which a temperature alarm sets off.
Critical temperature
alarm
Specify what is the absolute maximum temperature allowed in the house (ranges
from 0.5 above the house set point to 120ºF (48.9°C)). *Accessible if the outside
temp. sensor is enabled
Water 1 spill limit
Specify the maximum amount of water that can be consumed in a 15-minute delay.
This parameter ranges from 1 to 10,000 liters(1 to 2, 641 gallons)/15 min . *This
parameter is accessible if the water meter is enabled.
Water 1 high alarm
usage
An alarm is set off if the water consumption measured by a water meter in the last
24 hours is too high compared to the consumption measured in the 24 hours that
precede. Set the high alarm limit of each water meter separately. To disable this
monitoring function, decrease the parameter value until the word
Off
is displayed.
*This parameter is accessible if the water meter is enabled.
Water 1 low alarm
usage
An alarm is set off if the water consumption measured by a water meter in the last
24 hours is too low compared to the consumption measured in the 24 hours that
precede. Set the low alarm limit of each water meter separately. To disable this
monitoring function, decrease the parameter value until the word
Off
is displayed.
*This parameter is accessible if the water meter is enabled.
Disable low/high
water
If a high or low water consumption alarm is on, select
Yes
to acknowledge the
alarm condition. Note that when a reset is made, the controller needs 48 hours to
gather new consumption data before it can start monitoring the high/low water con-
sumption alarms again (no consumption alarms can happen by the end of this 48-
hour delay). *This parameter is accessible if a high or a low water consumption
alarm is on.
Static pressure alarm
units
*Accessible if a SP probe is enabled
890-00081
Expert VT-110
67
Содержание Expert VT-110
Страница 1: ...Expert VT 110 User Manual 890 00081 Version 24 REV 19...
Страница 6: ...NOTES 6 890 00081 Expert VT 110...
Страница 10: ...NOTES 10 890 00081 Expert VT 110...
Страница 12: ...NOTES 12 890 00081 Expert VT 110...
Страница 22: ...NOTES 22 890 00081 Expert VT 110...
Страница 26: ...NOTES 26 890 00081 Expert VT 110...
Страница 32: ...NOTES 32 890 00081 Expert VT 110...
Страница 46: ...NOTES 46 890 00081 Expert VT 110...
Страница 50: ...Chapter 13 Stir Fan 50 890 00081 Expert VT 110...
Страница 52: ...NOTES 52 890 00081 Expert VT 110...
Страница 64: ...NOTES 64 890 00081 Expert VT 110...
Страница 76: ...NOTES 76 890 00081 Expert VT 110...
Страница 78: ...NOTES 78 890 00081 Expert VT 110...
Страница 79: ...A Worksheets 890 00081 Expert VT 110 79...
Страница 80: ...Appendix A Worksheets 80 890 00081 Expert VT 110...
Страница 81: ...Appendix A Worksheets 890 00081 Expert VT 110 81...
Страница 82: ...NOTES 82 890 00081 Expert VT 110...