Total open
Enter the
exact time
that is required to reach the
actuator’s maximum limit switch. The controller will
limit the opening of the inlet according to this param-
eter value. *This parameter is accessible if the air
inlet uses a timer.
Under Run Open Time (for timer-based inlets only)
When a timer ends, it may take a few seconds for
the actuator to actually stop moving. For this
reason, the controller can switch off the actuator’s
motor slightly before its time for the actuator to
reach its exact moving time without exceeding it.
This parameter ranges from 0 to 3 seconds.*This
parameter is only shown if the inlet uses a timer and
it is only accessible with the factory password.
Calibrating the Inlets
If the inlet uses a potentiometer, the inlet’s actuator must be calibrated. This calibration indicates the mini-
mum and maximum positions of the actuator. The minimum calibrated position is a 0% opening and the
maximum calibrated position is 100%.
Before You Begin
Tip
For more accurate results, make sure at least 12 inches (30 cm) separates the minimum actuator’s posi-
tion from its maximum position.
1. Using the menu select arrow keys, navigate to
Inlet→Stage Opening
.
This menu is accessible if an inlet is enabled.
2. Calibrate the minimum position. Proceed as follows:
a. Close the inlet to its minimum position using the
Close
switch.
b. Once the inlet is closed, set the manual control switch to
Off
to stop the actuator.
NOTE:
This parameter is only accessible if the inlet uses a potentiometer.
3. Once the minimum position is calibrated, set the minimum parameter onscreen to
Yes
.
The word
Save
is displayed for 5 seconds onscreen and the minimum position is saved.
4. Calibrate the maximum position. Proceed as follws:
a. Open the inlet to its maximum position using the
Open
switch.
b. Once the inlet is fully open, set the manual control switch to
Off
to stop the actuator.
5. Now that the maximum position is calibrated, set the maximum parameter onscreen to
Yes
.
The word
Save
is displayed for 5 seconds onscreen and the minimum position is saved.
6. Set the manual control switch back to the “Auto” position to enable the automatic control of the inlet.
Configuring the Inlet Resets
What You Should Know
This menu is accessible if a timer-based inlet is enabled.
890-00081
Expert VT-110
43
Содержание Expert VT-110
Страница 1: ...Expert VT 110 User Manual 890 00081 Version 24 REV 19...
Страница 6: ...NOTES 6 890 00081 Expert VT 110...
Страница 10: ...NOTES 10 890 00081 Expert VT 110...
Страница 12: ...NOTES 12 890 00081 Expert VT 110...
Страница 22: ...NOTES 22 890 00081 Expert VT 110...
Страница 26: ...NOTES 26 890 00081 Expert VT 110...
Страница 32: ...NOTES 32 890 00081 Expert VT 110...
Страница 46: ...NOTES 46 890 00081 Expert VT 110...
Страница 50: ...Chapter 13 Stir Fan 50 890 00081 Expert VT 110...
Страница 52: ...NOTES 52 890 00081 Expert VT 110...
Страница 64: ...NOTES 64 890 00081 Expert VT 110...
Страница 76: ...NOTES 76 890 00081 Expert VT 110...
Страница 78: ...NOTES 78 890 00081 Expert VT 110...
Страница 79: ...A Worksheets 890 00081 Expert VT 110 79...
Страница 80: ...Appendix A Worksheets 80 890 00081 Expert VT 110...
Страница 81: ...Appendix A Worksheets 890 00081 Expert VT 110 81...
Страница 82: ...NOTES 82 890 00081 Expert VT 110...