AP CG-05 Скачать руководство пользователя страница 1

 

 

 

AUTOMATIKPRODUKTER 

 
 
 
 

 
 
 
 

Gas Controller  

CGM, CGD,PCR, CG-05

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

User’s Manual 

 

June 2012 

 
 
 
 
 
 
 

Содержание CG-05

Страница 1: ...AUTOMATIKPRODUKTER Gas Controller CGM CGD PCR CG 05 User s Manual June 2012...

Страница 2: ...ng Mode 13 4 5 4 Horn Function 13 4 5 5 External Operation of Alarm Relay 14 4 5 6 Delay Mode of Alarm Relay 14 4 6 Menu MP Parameter 15 4 6 1 Activate Deactivate MP 16 4 6 2 Lock or Unlock MP 16 4 6...

Страница 3: ...10 Define the Failure Relay 28 4 8 11 Acknowledge a Relay in Latching Mode by a DI 28 4 8 12 Power On Time 28 4 8 13 Registration of Expansion Modules 28 4 8 14 Error Indicator System Bus 29 4 8 15 An...

Страница 4: ...controller The total number of connected transmitters however may not exceed 96 respectively 98 transmitters Up to five free programmable alarm thresholds are available for each transmitter For transm...

Страница 5: ...s when alarm one or more alarms are active Permanently on when at least one relay is manually operated LED red Flashes when alarm two or more alarms are active Permanently on when at least one relay i...

Страница 6: ...nded for the service technician of the installer to change parameters and set points All settings can be edited with this password Priority 2 fixed value not changeable With code level 2 it is possibl...

Страница 7: ...errors See from point 4 1 Display of the status of actual alarms See point 4 2 Display of the relay status Manual operation of the relays Reset function of the relays See from point 4 3 Display of th...

Страница 8: ...ed in addition 4 1 1 Acknowledge a Fault Attention According to the directives of the gas measuring technique accumulated errors aren t allowed to be acknowledged automatically Therefore acknowledgmen...

Страница 9: ...transmitter not calibrated or defective Solution Check cable to analog transmitter make calibration replace the analog transmitter PE00 Error Internal communication error I O Board to LCD Board Cause...

Страница 10: ...OFF Relay manual ON Relay in latching mode 4 3 1 Manual Operation of the Relays The manual operation of the alarm relays is managed in the menu Status Relay or externally via an assigned digital inpu...

Страница 11: ...addresses MP01 to MP48 are listed with the index XX 1 for the measured value of the bus transmitter and with XX 2 for the measured value of the analog transmitter MP addressing mode 98 bus transmitte...

Страница 12: ...Relay Mode Definition of the relay mode Symbol Description Setting Status Function R 01 Relay No Selection of relay De energized Relay Mode De energized Relay de energized Relay energized Alarm OFF Re...

Страница 13: ...two parameters time or digital input is set This function has priority to the latching mode function The following possibilities to reset are available for the alarm relay as horn relay By pressing a...

Страница 14: ...to the parameter settings static flashing and energized de energized If external ON and OFF are parameterised on the same relay simultaneously and the both are active at the same time then only the si...

Страница 15: ...2 Parameter analog transmitter Activate or deactivate MP See 4 6 1 Lock or unlock MP See 4 6 2 Definition of gas type unit and number of alarms at falling concentrations AF See 4 6 3 Definition measu...

Страница 16: ...functionality is available from version 9 02 In the Lock Mode the function of the existing transmitter is put out of service which means there is no alarm or fault message at this measuring point Exis...

Страница 17: ...apours Ex infrared Nitrogen trifluoride Percentage Empty ppm LEL ppm ppm ppm Vol ppm ppm ppm ppm ppm Vol ppm ppm ppm ppm ppm ppm F C RH ppm LEL LEL LEL ppm 0 300 0 100 0 50 0 25 0 300 0 25 0 2000 0 10...

Страница 18: ...ter with non linear output signal semiconductor 4 6 6 Threshold Hysteresis For each measuring point five alarm thresholds are available for free definition If the gas concentration is higher than the...

Страница 19: ...elay Each of the 5 alarms can be assigned to any physically existing alarm relay Unused alarms are not assigned to an alarm relay See also 4 8 16 Relay Multiplication Symbol Description Default Status...

Страница 20: ...een tested In this menu the parameters for the long term recording of the USB device are set Main menu See 4 7 1 See 4 7 2 See 4 7 3 See 4 7 4 See 4 7 5 4 7 1 Data Logger Switch On Off Starting the lo...

Страница 21: ...etc Time MP1 MP2 MP3 MP4 MP5 MP6 MP7 MP8 MP9 MP10 Or time MP1 1 MP1 2 MP2 1 MP2 2 MP3 1 MP3 2 MP4 1 MP4 2 MP5 1 MP5 2 09_50_02 0 20 20 28 0 0 0 0 09_50_03 0 20 20 28 0 25 29 0 09_50_04 0 20 20 28 0 25...

Страница 22: ...itten in the file Time MP Gas CV AV A1 A1R A2 A2R A3 A3R A4 A4R A5 A5R 09_49_47 MP 02 CO 84 40 R01 80 R02 09_49_47 MP 03 CO 194 40 R01 80 R02 100 R03 120 R04 09_50_02 MP 02 CO 20 09_50_02 MP 03 CO 20...

Страница 23: ...rce Error date time Error type 10_22_28 MP 79 03_30 10_20 MP79 error 13_48_28 MP 79 03_30 13_46 MP79 error The first column gives the current time the second one the error source The third column indi...

Страница 24: ...1 See 4 8 2 See 4 8 3 See 4 8 4 See 4 8 5 See 4 8 5 See 4 8 6 See 4 8 6 See 4 8 7 See 4 8 7 See 4 8 7 See 4 8 8 Software Version CGD 05 XX Next maint Date TT MM JJ System Parameter Service Mode OFF S...

Страница 25: ...See 4 8 15 See 4 8 15 See 4 8 16 See 4 8 16 See 4 8 16 Fault Relay 05 Power ON time 30 s Missing Wrong 0 0 Analog Outputs Analog Output 1 Max Calibration AO 1 4 0 4 mA 20 20 0 PE Module 0 Relay active...

Страница 26: ...ddressing is influenced by it Symbol Description Default Status Function 98 Addr a 1 MP MP Addr Mode 98 Addr a 1 MP 98 Adr 1 MP only bus transmitters 48 Adr 2 MP bus transmitters analog transmitters 4...

Страница 27: ...sec Time for calculating the average value 4 8 7 System Time System Date Input and correction of time and date Selection of time and date format Symbol Description Default Status Function EU Time for...

Страница 28: ...arted at the Gas Controller after switching on of the power supply While this time is running out the Gas Controller does not activate alarms The power on status occurs on the first line of the starti...

Страница 29: ...A higher error rate mostly comes from incorrect laying of the field bus line 4 8 15 Analog Output The Gas Controller Module as well as the PE 05 Modules 1 to 5 have two analog outputs AO with 4 to 20...

Страница 30: ...d in this table Number Description Default Status Function 0 30 IN Relay 0 0 Function off X Relay X should be multiplied information source 0 30 OUT Relay 0 0 Function off X Relay X should switch toge...

Страница 31: ...ation techniques and with codes standards and proper safety procedures for control installations and the latest edition of the National Electrical Code ANSI NFPA70 It is also essential to follow stric...