Specifications
2-2
2.2 Performance specifications
Items
Specifications
Transmission clock
27 kHz (37 μs)
Transmission method
DC power supply superimposed total frame, cyclic method
Synchronization
Frame/bit synchronization
Transmission protocol
AnyWire ASLINK protocol
Maximum number of bits
512 points (256 inputs, 256 outputs)
Number of connectable units 128 units max.
Transmission distance /
Supply current
Cable diameter
Transmission distance
DP-DN allowable
supply current
1.25 mm
2
50 m or less
MAX 2A
Over 50 m, 100 m or less
MAX 1A
Over 100 m, 200 m or less
MAX 0.5A
0.75 mm
2
50 m or less
MAX 1.2A
Over 50 m, 100 m or less
MAX 0.6A
Over 100 m, 200 m or less
MAX 0.3A
0.5 mm
2
50 m or less
MAX 0.8A
Over 50 m, 100 m or less
MAX 0.4A
Over 100 m, 200 m or less
MAX 0.2A
Error correction
Double check, chuck sum
RAS functions
Transmission cable disconnection detecting function, Transmission cable
short-circuit detecting function, Transmission circuit drive power supply
voltage drop detecting function, ID (address) duplication/no setting
detecting function
Applicable cable
General-purpose, 2-core/4-core cable (VCTF, VCT 0.75 to 1.25 mm2,
Rated temperature: 70
C)
General-purpose cable (0.75 to 1.25 mm2, Rated temperature: 70
C)
Dedicated flat cable (0.75 mm2 / 1.25 mm2, Rated temperature: 90
C)
Connection method
T-branching, multi-drop, star-branching, Tree-branching
Power supply
Voltage: 21.6 to 27.6 V DC (24 V DC -10 to +15%) Ripple: 0.5 V p-p or less
Recommended voltage: 26.4 V DC (24 V DC +10%)
To comply with the UL standard, be sure to use a 24 V DC stabilized power
supply for NEC Class 2 output.
Bit transmission cycle time
32 inputs
32 outputs
64 inputs
64 outputs
128 inputs
128 outputs
256 inputs
256 outputs
2.4 ms
3.6 ms
6.0 ms
10.7 ms
Power consumption
150 mA (not including the load)
Weight
200 g