P/N 1011965 Rev A 08/22

14

Initial Performance Verification

After initial flush, a TDS (Total Dissolved 

Solids) measurement should be taken 

and recorded. This data can be used to 

compare to factory test data and future 

system data. Some deviations may occur 

due to differences in feed water TDS and 

temperature
Total Dissolved Solids (TDS) Rejection 

Test
Use the TDS meter to measure the TDS 

in both the feed water and product water. 

Calculate the percent rejection using the 

formula below. Rejection should be 85% or 

better:

100 x (Feed TDS - Product TDS) / 

 

(Feed TDS) = % Rejection

Example:
Feed TDS = 500 ppm

 

Product TDS = 25 ppm

 

100 x (500 - 25) / (500) = 95% Rejection

RO Recovery Calculation

Using a stop watch and graduated cylinder 

(or other calibrated volume), measure the 

product water flow rate and the drain flow 

rate. The product water flow rate should 

be the flow coming directly from the RO 

System, not from the tank. Close the TDS 

blending valve and the tank valve to make 

this measurement. Calculate the percent 

recovery using the formula below:

100 x (Product Flow Rate) / (P 

Drain) = % Recovery

Example:
Product Flow Rate = 25 ml/min

 

Drain Flow Rate = 200 ml/min

 

100 x (25) / (25 + 200 ) = 11.1% Recovery

Recovery is dependent on feed water 

temperature and pressure. Measure and 

record the feed water temperature and 

pressure whenever measuring the percent 

recovery.

Semi-Annual Tasks

Check Tank Air Pre-Charge

The tank air charge should be checked 

every six months:
Tools and supplies required:
Air Pressure Gauge, 5-40 psi range (0.3 

- 2.7 bar) with tire valve (Schrader Valve) 

connection.
Source of compressed air (manual bicycle 

tire pump or air compressor).

CAUTION

Air pre-charge should be checked and 

adjusted under zero system pressure. 

The system must be depressurized 

before checking the tank pre-Charge. 

Do NOT adjust the tank air pre-charge 

with the system under pressure.

CAUTION

Be careful when adding air to the tank. Do 

NOT add too much air pressure to the tank.

1. 

Depressurize the system by closing 

the Inlet Valve and opening the tank 

valve. Make sure the tank is fully 

drained.

2. 

Unscrew the protective cap from the 

air valve on the tank.

3. 

Use the pressure gauge to check 

the tank pre-charge for pressure.

NOTE:

 If any water comes out of the 

air valve, the tank bladder has 

ruptured and the tank needs to 

be replaced.

4. 

Check the tank manufacturer for the 

recommended air pressure charge. 

If there is no recommendation, 

most RO system tanks have an air 

pressure charge of 5-8 psi. 

 

y

To add pressure to the tank, use 

a manual bicycle tire pump or 

other source of compressed air.

 

y

To release pressure from 

the tank, press the center 

pin on the air inlet valve.

5. 

Once the tank air charge is set, 

replace the protective cap on the air 

valve. 

6. 

Pressurize the system by opening 

the Inlet and Tank valves.

Annual Tasks

Change Sediment, Carbon, and 

RO Cartridges

The sediment and carbon cartridges should be 

changed as indicated on the controller.

Depending on performance changes, the RO 

cartridge may need to be changed as indicated 

on the controller.

Follow the change procedures for each as 

shown earlier in this Maintenance section.

Содержание 9710161

Страница 1: ...rse Osmosis System Owner s Manual Models AQ RO 400 AQ RO 400 NT AQ RO 600 AQ RO 600 NT Manufacturing Numbers 9710161 9710162 9710163 9710164 www antunes com CAUTION Read all instructions before using the unit Original Instructions ...

Страница 2: ...Service at 1 877 392 7854 toll free Fill in the information in the next column and have it handy when calling for assis tance The serial number is on the specifi cation plate located on the system Purchased From Date of Purchase Model Number Serial Number Mfg Number Suggested replacement period for the RO Cartridge is 1 year IMPORTANT This equipment is to be installed to comply with the basic plum...

Страница 3: ...lt Protect from direct sunlight or other UV sources Avoid long term exposure to direct sunlight or other UV sources The RO should be stored in a dark location Protect from high temperatures or abrupt variation in temperature The maximum operating temperature is 100 F 38 C Avoid abrupt variations in temperature Any temperature variation should be made slowly Protect from rough handling or dropping ...

Страница 4: ... 400 NT Reverse Osmosis Cartridge Single Pack 7002303 AQ RO 600 AQ RO 600 NT Reverse Osmosis Cartridge Single Pack 7002304 Replacement Cartridges CAUTION When installed on metallic plumbing a properly sized electrical bonding jumper must be installed across the inlet and outlet pipes serving this unit CAUTION To ensure proper installation wall anchors for unit must be rated for AT LEAST 60lbs 30 k...

Страница 5: ...ximum Operating Temperature 100 F 38 C 100 F 38 C pH Range 4 10 4 10 Maximum Total Dissolved Solids TDS 1 000 ppm 1 000 ppm Maximum Hardness 60 gpg 60 gpg Silt Density Index 5 5 Iron Hydrogen Sulfide or Manganese 0 0 Nominal Capacity 400 600 Membrane performance after 24 hours at 77 F 25 C 500 ppm TDS and 70 psig Membrane performance after 24 hours at 77 F 25 C 500 ppm TDS and 80 psig Performance ...

Страница 6: ...nued to be filtered but the system will not flush This will cause the RO membrane to plug prematurely and reduce the life of the RO System y Tank Full Mode When the tank is full no water runs out of the drain line CAUTION Stopping the drain flow can cause the Filter to plug prematurely and may reduce the life of the filter Consult the factory for more information Figure 1 System Components Figure ...

Страница 7: ...nstallation The following tools and supplies are sug gested to help with the installation y Screwdriver y Adjustable Wrenches y Drill with Bits y Level y Tape Measure y Pipe Dope or Thread Seal Tape y Two Gallon Bucket y Fresh Unscented Liquid Chlorine Bleach y Pipe Wrenches y Hose or pipe for drain line Mounting the System The RO System comes with a Mounting Bracket for the system When mounting t...

Страница 8: ...on the air inlet valve 3 Once the tank air charge is set replace the protective cap on the air valve Drain Connection The drain is for flushing particle buildup out of the system during operation Install a sufficient length of 3 8 OD tubing not supplied from the drain outlet on top of the RO system to the drain When connecting the drain hose pay at tention to the following guidelines y The drain l...

Страница 9: ... starts to calculate When the running time is activated on the RO membrane the RO membrane lifetime is based on the calendar time and running time which value is reached first Items Status Filters F1 Prefilter a 10 100 Life Always on b 0 10 Life Symbol Flickering c 0 Life Symbol Off Maintenance IL on Buzz 3 times min F2 Carbon F3 RO Membrane Status PROCESSING a Letter on flickering system flushing...

Страница 10: ...the Pre filters and RO Membrane The white sediment prefilter must be installed in the left prefilter housing closest to the water inlet The carbon prefilter must be installed in the right prefilter housing after the sediment prefilter The RO membrane must be installed with the brine seal on the right nearest to the RO membrane housing inlet It should only be inserted into the RO housing from the r...

Страница 11: ... and let water into the system 6 Plug the power cord into an outlet The pump will come on and air in the pre filters and RO membrane will come out Wait 5 10 minutes until all air has been removed 7 Adjust the brine control valve so that the pressure gauge is 80 psi Opening the brine control valve increases the brine flow rate and lowers the membrane pressure and product water flow rate 8 Continue ...

Страница 12: ...RO The system is now ready for use Maintenance Replacing the RO Cartridge NOTE Always install a new Carbon cartridge after replacing the RO Cartridge 1 Turn off water to the system by closing the feed water valve and unplug the system power cord from the outlet 2 Close the tank valve 3 Depressurize the system 4 Pull out the tube which is inserted into the RO housing s inlet 5 Using the supplied wr...

Страница 13: ...rd the date the cartridges where changed and the next change date Replacing the Sediment Prefilter Cartridge NOTE Always install a new Sediment Prefilter Cartridge when replacing the Carbon cartridge 1 Turn off the water to the system by closing the feed water valve 2 Close the tank valve 3 Open a valve on the line to the store to depressurize the system 4 Unscrew the bowl and remove the old sedim...

Страница 14: ...lies required Air Pressure Gauge 5 40 psi range 0 3 2 7 bar with tire valve Schrader Valve connection Source of compressed air manual bicycle tire pump or air compressor CAUTION Air pre charge should be checked and adjusted under zero system pressure The system must be depressurized before checking the tank pre Charge Do NOT adjust the tank air pre charge with the system under pressure CAUTION Be ...

Страница 15: ... cartridges Storage shipping solution not completely rinsed out of the system Rinse the system for a longer period of time replace carbon cartridges Biological growth in pipes Sanitize plumbing Water conditions changed Consider installing additional filtration Broken membrane in RO Cartridge Replace RO Cartridge Flush runs continuously Tank pressure switch stuck open Replace tank pressure switch W...

Страница 16: ...s Exploded View 73 32 32 1 43 51 72 62 21 21 13 24 19 24 13 21 41 41 61 4 23 56 21 57 56 37 18 13 36 13 37 18 46 45 53 53 35 40 54 16 22 48 52 14 16 13 17 27 25 16 13 2 49 63 6 20 31 50 29 30 15 16 26 55 60 21 59 19 20 13 25 40 54 55 38 38 78 74 ...

Страница 17: ...ESSURE GAUGE PANEL MOUNTED 1 36 2170212 BLEND VALVE 3 8 TUBE PANEL MOUNTED 1 37 2180495 FILTER BOWL 2 38 2180495 FILTER HEAD 2 39 2180495 FILTER O RING 2 40 2180772 MOUNTING CLIP RO HSG 2 41 2180779 HOUSING BOWL AND HEAD RO 1 42 2180823 GLUE BOX RO CONTROLLER 1 43 2180824 SUPPORT FRAME RO CONTROLLER 1 44 2180825 PLASTIC CLIP M4 x 6 3mm 4 45 2190251 ADAPTOR TUBE TO 1 2 NPT 1 46 2190252 ADAPTOR 1 2 ...

Страница 18: ...ure F Feed Pressure psig Product Flowrate ml min Drain Flowrate ml min Percent Recovery Product TDS ppm Feed TDS ppm Percent Rejection Date Date Date Changed Sediment Next Sediment Change Changed Carbon Next Carbon Change Changed RO Next RO Change ...

Страница 19: ...P N 1011965 Rev A 08 22 19 Notes ...

Страница 20: ...nance calibration or regular adjustments as specified in operating and maintenance instructions of this manual and or labor involved in moving adjacent objects to gain access to the Equipment 2 Antunes reserves the right to make changes in design or add any improvements on any product The right is always reserved to modify equipment because of factors beyond our control and government regulations ...

Отзывы: