Antunes Controls G Series Скачать руководство пользователя страница 1

Installation Information

Gas Pressure Switches

Specifications

Antunes Controls Gas Pressure Switches monitor gas 
pressure.  The models are available in high pressure and 
low pressure single gas switches.  Pressure range varies 
from .5” of water column to 4 psi.

Each switch is adjustable within its range, as shown on the 
range scale located on top of the unit.  The latch button 
in the reset models, and the optional neon light indicate 
whether the switch is on or off.

These units do not require venting to atmosphere. 

 
 

Model-G

GGI 1010810019 Rev. A  05/07

R L

Automatic Reset

Manual Reset

WARNING

Read these instructions carefully before attempting 
to install, operate or service this switch. 
Failure to observe safety information and comply 
with instructions could result in personal injury, 
death and/or property damage. 
To avoid electrical shock or damage to equipment, 
disconnect power before installing or servicing. 
To avoid potential fire and/or explosion, do not use 
in potentially flammable or explosive atmosphere. 
Retain these instructions for future reference.  You 
must review your application and national and 
local codes to ensure that your installation will be 
functional and safe.

Содержание G Series

Страница 1: ... venting to atmosphere Model G GGI 1010810019 Rev A 05 07 RL Automatic Reset Manual Reset WARNING Read these instructions carefully before attempting to install operate or service this switch Failure to observe safety information and comply with instructions could result in personal injury death and or property damage To avoid electrical shock or damage to equipment disconnect power before install...

Страница 2: ...g on Switch Operation Connect to Normally OPEN NO or Normally CLOSED NC Cutaway View of Switch to Show Connection to Ground Connect Separate Ground Wire to Ground as Shown if required by local electrical code CONDUIT CONNECTIONS COM nC nO GROUnD Din COnneCtOR wiRinG Pressure Ratings Adjustable Operating Pressure 5W C to 4 psi different ranges Surge Pressure 15 psi 1 Bar NOTE To avoid initial line ...

Страница 3: ...nt All Models To adjust gas pressure cut off setting remove the cover Turn the range scale adjustable knob Figure 6 clock wise to increase pressure setting counterclockwise to decrease pressure setting Install cover and tighten the two cover screws to prevent tampering Figure 6 Figure 1 Figure 5 Figure 2 Figure 3 Figure 4 RANGE SCALE ADJUSTABLE KNOB RESET BUTTON RHGP G or RLGP G HGP G or LGP G Opt...

Страница 4: ... Single Unit Hi Pressure RHGP G These part numbers are for standard N P T gas inlet and electrical knockout NOTE For optional NEMA 4 Kit 4 Pin DIN Connector Neon Lamp Indicator or Side Mounting contact Antunes Controls for specific part numbers Optional Contact Antunes Controls NEMA 4 IP 65 Kit available Part No 808000404 4 Pin DIN Connector Neon Lamp Indicator Side Mounting It is understood and a...

Отзывы: