A-18
Addresses for Hardware Points
Overview
The AUTOPULSE Z-28 FACP contains many different types of points -- including read-only
system points, SLCnet channel points, points on optional cards, digital and analog pseudo
points, list points, and card status (trouble) points. Many of these points may be referenced,
using the point’s address, in Custom Control equations.
This section provides a card-by-card description of the AUTOPULSE Z-28’s hardware,
pseudo, and list points. Card Status points, which may only be viewed from the Active
Trouble List, the Historical Logs, or on an RS-232 port (if available), are not discussed in this
section.
Master Controller (SFI/O)
Hardware Points
The Master Controller (SFI/O) card resides at card address 0 and contains 13 hardware points.
In the table, each point has a type of R or U. Points listed with a type of R are reserved system
points. Points with a type of U are user-configurable.
Continued on next page
Table A-3. Master Controller (SFI/O) Hardware Points
Point
Type
Label
Description
0-1
R
Front Panel
Piezo
Indicates the status of the piezo sounder on the
AUTOPULSE Z-28
Master.
0-2
R
External N2
Disconnect
Relay
Indicates the status of the External N2 Disconnect
Relay. Turns on when no slaves are communicating;
turns off on System Reset.
0-3
R
Fire LED
Status of the front panel Alarm LED.
0-4
R
Supervisory
LED
Status of the front panel Supervisory LED.
0-5
R
Trouble LED
Status of the front panel Trouble LED.
0-6
R
Alarm Silence
LED
Status of the front panel Alarm Silence LED.
0-7
R
AC Power LED
Status of the front panel AC Power LED.
0-8
U
User LED 1
This point indicates the status and configuration of
the first user programmable LED on the front panel.
0-9
U
User LED 2
This point indicates the status and configuration of
the second user programmable LED on the front
panel.
0-10
U
User LED 3
This point indicates the status and configuration of
the third user programmable LED on the front panel.
0-11
U
User Defined
Key 1
This point indicates the status and configuration of
the first user programmable key (in the function
menu).
0-12
U
User Defined
Key 2
This point indicates the status and configuration of
the second user programmable key (in the function
menu).
0-13
R
LCD Backlight
Indicates the status of the LCD backlight on the front
panel.