![Ansul AutoPulse Z-28 Скачать руководство пользователя страница 138](http://html1.mh-extra.com/html/ansul/autopulse-z-28/autopulse-z-28_instructions-manual_2946331138.webp)
Step 4. Edit An Output Statement’s Properties,
Continued
10-18
Continued on next page
Opcode
Qualifier
Application
Hold
PRI
When the input side of the equation is true, the priority is reset to the value
specified until a system reset is performed.
Slow March
Time
When the input side of the equation is true, the output cycles at 20 beats per
minute (bpm) until a system reset is performed.
Fast March
Time
When the input side of the equation is true, the output cycles at 120 beats per
minute (bpm) until a system reset is performed.
Temporal
When the input side of the equation is true, the output pattern consists of three
½ second pulses, each separated by ½ second of silence. Each group of three
cycles is separated by 1.5 seconds of silence. The output cycles until a system
reset is performed.
Track
ON
When the input side of the equation is true, the output turns ON. When the
input is false, the output turns OFF.
OFF
When the input side of the equation is true, the output turns OFF. When the
input is false, the output turns ON.
PRI
When the input side of the equation is true, the priority is changed to a value
that you specify. When the input is false, the priority returns to its original
value.
Set
On
When the input side of the equation is True, Set turns the point referenced on
the output side of the equation ON. The point stays ON until a Set OFF
command occurs.
OFF
When the input side of the equation is True, Set turns the point referenced on
the output side of the equation OFF. The point stays OFF until a Set ON
command occurs.
PRI
When the input side of the equation is True, Set turns the point referenced on
the output side of the equation ON. The point stays ON until a Set OFF
command occurs.
Enable/
Disable
On
When the input side of the equation is true, the enable/disable state of the point
is set to ON, which disables the point.
OFF
When the input side of the equation is true, the enable/disable state of the point
is set to OFF, which enables the point.
Set Analog
Value
Constant
When the input side of the equation is true, the value of an analog pseudo point
is set to a constant value.
Variable
When the input side of the equation is true, the value of an analog pseudo point
is set to a variable value.
Table 10-2. Output Opcodes and Qualifiers
, continued