andrews PAC15 Скачать руководство пользователя страница 1

Click

 www.andrews-sykes.com

or Call Us Free

 0800 211 611

PAC15

 

Portable Air Conditioning 

Operating Instructions 

& Safety Guide

General Safety

   Keep children and animals away from air conditioning units. Never   

leave them alone in a room where the units in use.

   This equipment should only be used by a competent person who    

has read and understood these instructions.

    Never operate this equipment if you are ill, feeling tired or under the  

 

influence of alcohol or drugs.

  Keep the Air Conditioning vents clear of all obstructions.
  Never put anything on top of the unit or block the air outlets.
  Make sure equipment is switched off and unplugged after use.  
  Never leave switched on or unattended. 
   Do not use the unit where sunlight is shining directly onto it.
   Check condition of equipment before use. If unit is showing signs    

of damage contact your supplier immediately.

Electrical Safety

   This unit requires a 230 volt electrical supply. It plugs into a standard bs1363 

domestic socket.

   Always inspect plugs and leads for damage before plugging into the supply - 

DO NOT UsE IF ANY DAMAGE Is FOUND

  Ensure cables are run as not to cause a hazard.
   If an extension lead is used, ensure it is of the correct standard , and fully 

uncoiled when being used. 

  Do not lay electrical cables in wet / damp areas.
  Do not move equipment whilst operating. 
  Do not pull equipment by its cable. 

   It is recommended that electrical equipment is used via a suitable RCD.

Machine not working?

ONLY A COMPETENT ELECTRICIAN sHOULD ATTEMPT TO RECTIFY 
ELECTRICAL sUPPLY PRObLEMs. DO NOT REMOVE ANY PANELs FROM  
THE MACHINE. 

Problem

Likely Cause

Solution

No air flow from the 
room unit

Red ‘MAINs’ light off

Turn on electricity and/or check mains 
supply fuse

No air flow from the 
room unit

Red ‘MAINs’ light on. 
White ‘DEFROsT’ 
light on

Machine is in defrost mode, do not 
adjust anything, machine will revert to 
normal run after 10 mins

Insufficient air flow 
from the room unit

blocked air filter

Clean filter

No cooling

Green ‘COOLING’ 
light off

Revolve thermostat knob fully anti-
clockwise to ‘1’. Wait 10 minutes for 
time delay on start-up.

No cooling

Amber ‘ATTENTION’ 
light illuminated. High 
pressure trip.

Press ‘+’ button to re-set and check for:

Lack of water flow...kinked hoses?

shortage of water..... top up.

External heat exchanger unit mounted in 
very high temperature?

Water frozen? Add glycol (33%)

External heat exchanger coil blocked 
with dirt.... clean

Air cooled units.... lack of air flow from 
exhaust.... kinked or blocked duct, duct 
too long.

No cooling

Amber ‘ATTENTION’ 
light illuminated. Low 
pressure trip.

Press ‘-’ button to re-set and check for:

No air flow, blocked filter?

Evaporator blocked with ice. Very low air 
temperature?

No cooling

Amber ‘ATTENTION’ 
light illuminated. High 
level condensate trip.

Condensate pump not reducing water 
level. Kink in condensate tube between 
room unit and external heat exchanger? 
Leak inside room unit. Pump filter inside 
room unit blocked. Condensate tube frozen

Routine Maintenance

The air filter must be kept clean, never allow to become choked with dust or dirt. 
If allowed to do so, the performance of the unit will become impaired, resulting in 
loss of air flow, freezing up the evaporator coil and possible component damage. 

To access the filter, lift out the return air grille on the front face of the unit (fig. 4). On 
refitting the filter ensure that it is correctly positioned covering the whole face of the grille. 

The filter (see fig. 4) can be washed in warm, soapy water, rinsed and shaken dry 
before replacement. Frequency of cleaning depends upon application and can 

Fig. 4

Отзывы: