Andover Controls ACC EMX 150 Скачать руководство пользователя страница 1

Copyright © 1991 Andover Controls Corporation, 300 Brickstone Square, Andover, MA 01810  All Rights Reserved.

Click for EMX Menu 

Your warranty is effective for 18 months starting on the 
date the system is shipped.

Before You Begin

You can connect one or more EMX modules to most Infinet 
controllers that have an expansion port. The particular con-
trollers are covered in the ACC EMX Modules Configuration 
Guide
 (also enclosed with this product).The configuration 
guide also tells how many inputs and outputs are allowed for 
any a particular controller. Before you proceed, be sure the 
controller allows modules and the number and type of mod-
ules you plan to use. 

Warning

Be sure wiring and installations comply with local, state, 
and national electrical codes.

Figure 1 shows the EMX 150 module.

Figure 1.  The EMX 150 Module

Dimensions

Each EMX 150 module is approximately 6.13 

×

 4.88

 ×

 1.52 in.

Power Requirements

The first two modules receive power from the controller 
and operate on 24 to 26 VDC. You can add additional 
EMX modules other than an EMX 150 if you have an ex-

EMX150

BOARD

1

2

RET

I
V

OUTPUT

A

RET

I
V

OUTPUT

B

OVERRIDE

A

AUTO

MAN

B

A

B

EXTERNAL

POWER

ternal power supply source of 24 VDC and properly 
connect the modules to it. See the ACC EMX Modules 
Configuration Guide
 for more information.

The EMX 150 consumes up to 55 mA at 24 VDC.

Environmental Requirements

The EMX 150 operates in the same environment that any 
Infinet controller operates in.

Output Characteristics

The voltage output has 5 mA maximum output over the 
range of 0 to 20 VDC. The input impedance of the device 
being controlled can be no less than 4000 

.

Resolution of each voltage output is 0.100 V or 100 mV.

The current output has a 0 to 20 mA control signal.  The 
input impedance of the device being controlled can be no 
greater than 750 

.

The circuitry that produces the 0 to 20 mA signal acts as a 
“current sourcing device.” It sources the current to ground.

Resolution of each current output is 100 

µ

A or 0.1 mA.

Install the EMX 150

1. Unpack

Be careful when unpacking the unit or units to not damage 
the packaging material—you must reuse it if you ship the 
product back for repair.

2. Connect to the Infinet Controller

Connect the module to the Infinet controller as outlined in 
the steps that follow.

Caution

Be sure you disconnect the Infinet controller’s AC power 
source before you connect any modules.

ACC EMX 150
Installation Guide

Order No. 30-3001-198

Version 1.2

www.PDF-Zoo.com

Отзывы: